EasyManua.ls Logo

Baxi DUO-TEC COMPACT+ - ACCESSORIES NOT INCLUDED IN THE SUPPLY; External Sensor Installation; External Storage Boiler Connection; Connecting to a Zone System

Baxi DUO-TEC COMPACT+
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
INSTALLER Section (en)
7651556.01 (1-01/16)
11.2 ACCESSORIES NOT INCLUDED IN THE SUPPLY
11.2.1 EXTERNAL SENSOR
7RFRQQHFWWKLVDFFHVVRU\VHH¿JXUHWRVLGHWHUPLQDOV4-5)
DQGWKHLQVWUXFWLRQVVXSSOLHGZLWKWKHVHQVRU
SETTING THE "Kt" CLIMATE CURVE
When the external sensor is connected to the boiler, the
HOHFWURQLF ERDUG DGMXVWV WKH ÀRZ WHPSHUDWXUH FDOFXODWHG
according to the set KtFRHI¿FLHQW6HOHFWWKHUHTXLUHGFXUYHE\
pressing
as indicated in the chart in annex SECTION
E for selecting the most appropriate one (00 to 90).
KEY TO CHART - “SECTION” E
)ORZWHPS Outside temp
11.2.2 EXTERNAL STORAGE BOILER
The boiler can be electrically connected to an external storage boiler. A diagram of the hydraulic connection of the external
VWRUDJHERLOHULVVKRZQLQDQQH["SECTION" F. Connect the DHW priority sensor NTC to terminals 9-10 on terminal block M2.
7KHVHQVLWLYHHOHPHQWRIWKH17&VHQVRUPXVWEHLQVHUWHGLQWKHVSHFLDOZHOOORFDWHGRQWKHVWRUDJHERLOHU0DNHVXUHWKDWWKH
H[FKDQJHFDSDFLW\RIWKHVWRUDJHERLOHUFRLOLVDSSURSULDWHIRUWKHSRZHURIWKHERLOHU$GMXVW'+:WHPSHUDWXUH&&
by pressing
.
,03257$17VHWSDUDPHWHU3 DVGHVFULEHGLQVHFWLRQ
11.2.3 CONNECTING TO A ZONE SYSTEM
To use this function, install the programmable relay electronic board supplied as an accessory.
KEY TO ELECTRICAL CONNECTIONS (see diagram in annex "SECTION" G at the end of this manual).
Z Zone (1..n) EV Zone electrovalve
R Relay RT Room thermostat
7KHERLOHUFDQPDQDJHD]RQHKHDWLQJV\VWHP7KH5RRP8QLWZDOOPRXQWHGFDQEHXVHGWRFRQWURORQH]RQHZKLOHQRUPDO
ambient thermostats can be used to control the other zones.
SYSTEM CONNECTIONS
Connect the zone 1 valve/pump to terminals 1 - 3 of the relay board terminal block inside the boiler control box.
Connect the Ambient Thermostat contact of the other zones to terminals 1-2 of terminal block M1 (CONNECTING THE
AMBIENT THERMOSTAT section).
Check that parameter 3  Set parameter P10 (SETTING PARAMETERS section).
SIEMENS
QAC34
1
9
8
7
6
5
4
3
2
10
M2
CG_2394

Related product manuals