EasyManua.ls Logo

Baxi DUO-TEC COMPACT+ - COMBUSTION ANALYSIS AND ADJUSTMENT; Combustion Test (CO₂%); Combustion Adjustment Function (CO₂%); GAS VALVE

Baxi DUO-TEC COMPACT+
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
INSTALLER Section (en)
7651556.01 (1-01/16)
12.4 COMBUSTION TEST (CO
2
%)
For correct boiler operation, the content of (CO
2
- O
2
) in the combustion fumes must observe the tolerances indicated in the
IROORZLQJWDEOH,IWKHYDOXHRI&2
2
- O
2
) is different, check the electrodes and their relative distances. If necessary, replace the
HOHFWURGHVDQGSRVLWLRQWKHPFRUUHFWO\,IWKHSUREOHPSHUVLVWVXVHWKHIROORZLQJIXQFWLRQ
G20 G31
CO
2
%O
2
%CO
2
%O
2
%
0D[LPXPSRZHU
Nominal value 8.7 5.4 10.0 6.0
Permitted value 8.2 - 9.3 6.3 - 4.3 9.5 - 10.5 6.8 - 5.2
,JQLWLRQSRZHU
Nominal value 8.7 5.4 10.8 4.8
Permitted value 8.2 - 9.3 6.3 - 4.3 10.3 - 11.3 5.5 - 4.1
0LQLPXPSRZHU
Nominal value 8.8 5.2 10.0 6.0
Permitted value 8.2 - 9.3 6.3 - 4.3 9.5 - 10.5 6.8 - 5.2
7KHFRPEXVWLRQVDQDOLV\VVKDOOEHGRQHXVLQJDQDQDO\]HUUHJXODUO\FDOLEUDWHG
'XULQJQRUPDORSHUDWLRQWKHERLOHUSHUIRUPVFRPEXVWLRQFRQWUROF\FOHV,QWKLVSKDVH&2YDOXHVKLJKHUWKDQSSPFDQ
occur for brief periods of time.
COMBUSTION ADJUSTMENT FUNCTION (CO
2
%)
This function sets out to partially adjust the value of CO
2
%7KHIROORZLQJSURFHGXUHLVXVHG
• Press buttons and WRJHWKHUIRUDWOHDVWVHFRQGV:KHQWKHIXQFWLRQLVHQDEOHGWKHGLVSOD\VVKRZV³On´IRUDIHZ
VHFRQGVIROORZHGE\SURJUDPPHURZ³304´DOWHUQDWHGZLWKWKH%RIERLOHUSRZHU
$IWHUWKHEXUQHULVOLWWKHERLOHUUHYHUWVWRPD[LPXP'+:SRZHU:KHQWKHGLVSOD\VKRZV100LWLVSRVVLEOHWRSDUWLDOO\
adjust the value of CO
2
%
• press
7KHGLVSOD\VKRZV00DOWHUQDWLQJZLWKWKHIXQFWLRQQXPEHU304 ÀDVKHV
• press
WRUDLVHRUORZHUWKHDPRXQWRICO
2
(from -3 to +3).
• press
WR VDYH WKH QHZ YDOXH DQG YLHZ WKH SRZHU YDOXH  RQ WKH GLVSOD\ DJDLQ WKH ERLOHU FRQWLQXHV RSHUDWLQJ DW
PD[LPXP'+:SRZHU
This procedure can also be used to adjust the quantity of CO
2
to the LJQLWLRQSRZHU and to the PLQLPXPSRZHU by pressing
after point 5 of the procedure described above.
$IWHUVDYLQJWKHQHZYDOXHSRLQWRIWKHSURFHGXUHSUHVV to take the boiler to its LJQLWLRQSRZHU. Wait for the value of
CO
2
WRVWDELOLVHDQGWKHQDGMXVWDVGHVFULEHGLQSRLQWRIWKHSURFHGXUHWKHSRZHUYDOXHLVDQXPEHU!DQG!WKHQ
save (point 5).
• press
again to take the boiler to PLQLPXPSRZHU. Wait for the value of CO
2
to stabilise and then adjust as described in
SRLQWRIWKHSURFHGXUHSRZHUYDOXH 
to exit the function, press the buttons for at least 6 seconds as described in point 1.
13. GAS VALVE
This appliance does not require any mechanical adjustment on the valve. The system ensures electronic auto-adaptation.
*DVYDOYHNH\
Pi
Gas supply inlet pressure tap
13.1 GAS CONVERSION METHODS
Only an Authorised Technical Assistance Service can convert boiler operation from NATURAL GAS to LPG or vice-versa. To
perform calibration, set parameter P02 as described in the PARAMETER SETTINGS section. Lastly, check the combustion
parameters as described in the SPECIAL FUNCTIONS - CHECKING COMBUSTION PARAMETERS section.
:KHQWKHJDVFKDQJHLVFRPSOHWHGWKHERLOHUGDWDSODWHPXVWEHDPHQGHGWRLQGLFDWHWKHQHZJDVGDWD
Pi

Related product manuals