Parameterization and commissioning
BK3xx0 37Version: 4.3.0
Byte Bit Value Description GSD file
10 0-1 00
bin
Reaction to PROFIBUS error: K-bus cycle is abandoned (default,
digital outputs become 0, complex outputs are set to a configured
substitute value) (see Reaction to PROFIBUS errors [}69])
Standard
01
bin
Reaction to PROFIBUS error: K-bus outputs become 0
10
bin
Reaction to PROFIBUS error: K-bus outputs remain unchanged
10 2-3 00
bin
Reaction to K-bus error: DP data exchange is abandoned (default)
(see K-bus interruption [}69])
Standard
01
bin
Reaction to K-bus error: DP inputs set to 0
10
bin
Reaction to K-bus error: DP inputs remain unchanged
11 3-6 X Maximum length of the diagnostic data. Allowed values: 16, 24, 32, 40,
48, 56, 64 (see Terminal diagnosis [}70])
Extended
12 0-1 0
bin
If K-bus mode is synchronous: Standard synchronous mode (default)
(see K-bus cycle [}53])
Extended
01
bin
If K-bus mode is synchronous: synchronous mode with optimized input
update (one cycle)
10
bin
If K-bus mode is synchronous: synchronous mode with optimized input
update (two cycles)
12 4-7 0
bin
Maximum DP buffer lengths not changed Extended
12 4-7 15 The maximum DP buffer lengths are changed using the values from
UserPrmData 37-40 (see Multi-configuration mode [}73])
Extended
13 0-7 X
Delay time (in µs) high byte (see K-bus cycle [}53])
Extended
14 0-7 X
Delay time (in µs) low byte (see K-bus cycle [}53])
Extended
15-30 0-7 X
Assignment of Bus Terminals 1 to 64 (see Multi-configuration mode
[}73])
Extended
31-36 0-7 - Reserved Extended
37 0-7 X
Maximum length of the input data (see Multi-configuration mode
[}73])
Extended
38 0-7 X
Maximum length of the output data (see Multi-configuration mode
[}73])
Extended
39 0-7 X
Maximum length of the diagnostic data (see Multi-configuration mode
[}73])
Extended
40 0-7 X
Maximum length of the configuration data (see Multi-configuration
mode [}73])
Extended
41-56 0-7 X
Assignment of terminals 65 to 128 (see Multi-configuration mode
[}73])
Extended