Caution
Certain
component
parts
are factory sealed
and
are
designed
so as to
be
tamper
proof.
Usually
such
items
do
not
require
servicing,
and
therefore
should
not
be
tampered
with. Failure to
comply
with
this
can
invalidate
any
warranty,
and
can
also
lead
to
premature
failure.
The
foDowing
parts
fall
within
this category:
room
thermostat,
time
clock, frost
thermostat,
sequential
controller,
and
fan
and
motor.
Additionally,
the
fan
and
limit
stat
has
been
factory set,
and
must not be re-set
without
formal
consent
from Benson
Environmental
Ltd.
Reference
should
be
made
to
the
separate
information
covering
the
operational
details of the
burner
and
timer.
Only approved spare/replacement parts can be fitted, failure
to
comply with this can compromise
the safe and efficient running
of
the heater, and can also invalidate any warranty claim.
5.1 Planned Servicing
In
order
to
maintain
the
efficient
operation
of the
heater
it is
recommended
that
the following
planned
servicing
and
preventative
maintenance
programme
is
adopted
by
the
user.
Quarterly Inspection
(a)
Visual
inspection
of
the
burner
(b)
Clean
and
check
spark
electrode
(c)
Clean
and
check
photo
cell
(d)
Check
overheat
safety is
operational
Bi-Annual Inspection
(a)
As
per
quarterly
inspection,
plus
...
(b)
Combustion
check
(c)
Smoke
test
Annual
Inspection
(a)
As
per
half
year
inspection,
plus
...
(b)
Heat
exchanger
and
cleaning
(c)
Electrical
connections
(d)
Main
fan
motor
(e)
Main
fan
assembly
(f)
Pulleys
(g)
Fan belts
(h)
Oil
supply
including
filter
(i)
Burner
(j)
Air
delivery
system
(k)
Flue
(1)
Report