n
Pre-extinguishment Phase
If the programmed extinguishment conditions occur
(programmed by your Installer), the Extinguishment
Module will generate the Pre-extinguishment phase
which will be signalled by:
Ø
the devices set up by the installer;
Ø
the ON Pre Ext. LED (On).
The Extinguishment Module will activate the Fire Extin
-
guishment devices when the Pre-extinguishment Time
expires.
The Pre-extinguishment phase will allow you to check
whether use of these devices and Evacuation of the
premises are really necessary.
The Pre-extinguishment phase can be terminated by
means of the:
Ø
Disable Extinguish. button;
Ø
duly set up manual buttons.
+
The Disable Extinguish. button can be used du
-
ring Access Level 2 only.
n
Extinguishment Phase
The Extinguishment Module will activate the Fire Extin
-
guishment devices when the Pre-extinguishment Pha
-
se expires.
The Extinguishment Phase will be signalled by.
Ø
the ON Electrovalve LED (On).
The AV ACTIVATED event, and the respective details
will be recorded in the logger (EXTING.MODULE 1 or
EXTING.MODULE 1).
The Extinguishment Phase will run for the pre-set
Extinguishment Time or, until the Control panel Resets.
The Extinguishment Phase can be interrupted by the:
Ø
Disable Extinguish. button;
Ø
duly set up Inhibit Extinguishment call points.
+
The Disable Extinguish. button can be used du
-
ring Access Level 2 only.
If you re-enable the Extinguishment phase, it will not
start until the pre-set Pre-extinguishment Time ends.
If you restore the Inhibit Extinguishment call points to
standby status, the Extinguishment phase will restart
immediately.
n
Manual Extinguishment
The Extinguishment Module can be activated from ma
-
nual call-points (ask your Installer for details).
Manual activation of the Extinguishment Module is si
-
gnalled by:
Ø
the ON Manual Ext. LED (On);
Ø
a message on the display similar to the following:
EXTING.MODULE.1
MANUAL ACTIVATE
+
If you activate the Extinguishment Module ma
-
nually, the Control panel will generate an Alarm.
n
Disable Extinguish. button
This button will allow you to inhibit the Fire Extingui
-
shment devices.
+
The Disable Extinguish. button can be used du
-
ring Access Level 2 only.
This operation will be signalled by:
Ø
the Disable Extinguish. LED (On);
Ø
the Disab. LED (On).
The OUTS BYPASS event, and respective details will
be recorded in the logger (EXTING.MODULE 1 or
EXTING.MODULE 1).
If you disable the Extinguishment Module during
Standby status, it will be unable to operate in the event
of an Alarm.
If you disable the Extinguishment Module during the
Pre-extinguishment Phase, the Pre-extinguishment
Phase will be interrupted until the Extinguishment Mo
-
dule is re-enabled. The Pre-extinguishment Phase will
re-start from the point of interruption.
If you disable the Extinguishment Module during the
Extinguishment Phase, the latter will be interrupted.
n
Disable Manual Extinguish. button
This button will allow you to Disable/Enable manual ac
-
tivation of the Extinguishment Module.
+
The Disable Manual Extinguish. button can be
used during Access Level 2 only.
This operation will be signalled by:
Ø
the Disable Manual Extinguish. LED (On);
Ø
the Disab. LED (On).
USER’S INSTRUCTIONS 5