6. Settings
6.1 Setting of control and feed height
Item Description
A Control keyboard
B Company nameplate
961087_00
B
A
5 Automatic night reduction Aut.
If the forward flow temperature in the system decreases
by 10° to 15°C (min. 0.1°C/min.), the pump output
is reduced to «min. » after approx. 2 hours.
If the forward flow temperature increases by 10 °C,
changeover is made immediately to control operation.
LED lights: «Automatic night reduction» function
is connected.
Note:
At constant speed I, II or III, the automatic night
reduction is deactivated.
The following conditions must be satisfied
for the automatic night reduction to function properly:
The pump must be installed in the forward flow
of the heating.
It does not function in the return flow.
The heating must have a control for temperature
of the medium.
1 Control key
2 Controlled operation: Proportional pressure (pp)
Suggested for the following equipment:
Dual pipe systems with thermal valves and
long stretches of pipe
valves with a large working area
high pressure loss
Primary circuit pumps with high pressure loss
3 Controlled operation: Constant pressure (cp)
Suggested for the following equipment:
Dual-pipe systems with thermal valves and
Feed height <2m
Natural circulation (formerly gravity heating)
with very low pressure loss
Primary circulation pumps in systems
with low pressure loss
Floor heating with thermostatic valves
Single-pipe heating
4 Uncontrolled operation: Constant speed (cs)
The operating point can be optimally adjusted
by altering the speed (A2 buttons).
Suggested for systems with constant volume flow:
Air conditioning units, heat pumps, boiler feed pumps, etc.
1
5 6
2 3 4
6 The indication shows the present power consumption
of the pump with the mains supply switched on.
A malfunction of the pump is indicated with «- -».
See section 9 for elimination (fault summary).
The AXW 10
has no setting options!