.4.2 CM-SW-01
Standard for all CSW105 compressors
The compressor module integrates the entire electronic
periphery of the compressor: It allows monitoring the
essential operating parameters of the compressor: mo-
tor and discharge gas temperature, phase and rotation
direction monitoring, oil supply and application limits
and thus protects the compressor from operation under
critical conditions. For further information, see Tech-
nical Information ST-150.
!
!
NOTICE
The compressor module may be damaged or
fail!
Never apply any voltage to the terminals of CN7
to CN12 not even for test purposes!
The voltage applied to the terminals of CN13
must not exceed 10V!
The voltage applied to terminal 3 of CN14 must
not exceed 24V! Do no apply voltage to the
other terminals!
The following components are completely installed and
wired in the state of delivery:
Slider position indicator.
Oil monitoring (OLC-D1).
Solenoid valves for capacity control and V
i
.
Discharge gas temperature sensor.
Low pressure and high pressure transmitter.
Modification to these components or their wiring is not
required and should not be done without consulting
BITZER.
The following components are not installed and wired in
the state of delivery and need to be connected:
Motor temperature monitoring (PTC sensor in motor
winding).
Phase monitoring (in case of a phase failure or inad-
missibly high phase asymmetry).
The compressor module internally supplies voltage to
the peripheral devices (solenoid valves, oil monitoring
device and slider position indicator) and to the terminal
strips CN7 to CN12.
Please refer to the Technical Information ST-150 for in-
formation on all connections.
5
.4.3 SE-i1
This protection device with extended monitoring func-
tions can be used as an option for all HS.53 .. HS.85
compressors and CSH and CSW compressors.
Monitoring functions:
Temperature monitoring.
Monitoring of the PTC control circuit to detect any
short-circuit or line break/sensor failure.
Rotation direction monitoring.
Monitoring of phase failure and asymmetry.
Monitoring of the maximum cycling rate.
For further information, see Technical Information
CT-110.
5
.4.4 SE-E2
Optional protection device for operation with frequency
inverter and soft starter (for a ramp time shorter than
1s).
Dimensions and integration in the control identical to
SE-E1.
Suitable for all CS. compressors.
Monitoring functions are basically identical to those
of SE-E1. However, the SE-E2 monitors phase fail-
ure during the entire running time of the compressor.
For further information, see Technical Information
ST-122.
5
.4.5 Monitoring of the oil circuit
For short circuits without liquid injection (LI) for addi-
tional cooling and for small system volume and small
refrigerant charge: Indirect monitoring with oil tem-
perature sensor (standard)
!
!
NOTICE
Lack of oil leads to a too high increase in tem-
perature.
Risk of damage to the compressor!
For circuits with liquid injection (LI) for additional
cooling and / or for great system volume as well as
parallel compounding: Monitor oil level directly with
opto-electronic oil level monitoring (option), see
chapter Opto-electronic oil level monitoring OLC-D1-
S, page 26. The connection is on the compressor
housing, see chapter Connections and dimensional
drawings, page 14, position 8.
SB-170-9
Semi-hermetic compact screw compressors
Translation of the original Operating Instructions
English....................................................................................................................................................... 2
Halbhermetische Kompaktschraubenverdichter
Originalbetriebsanleitung
Deutsch ..................................................................................................................................................... 35
Compresseurs à vis compacts hermétiques accessibles
Traduction des instructions de service d'origine
Français..................................................................................................................................................... 68
CSH6553-35Y..CSH6593-60Y
CSH7553-50Y .. CSH7593-110(Y)
CSH8553-80Y .. CSH8593-180(Y)
CSH9553-180(Y) .. CSH95113-320Y
CSH7673-70Y .. CSH7693-90Y
CSH8673-110Y .. CSH8693-140Y
CSH9663-160Y .. CSH96113-320Y
CSK6151-50 .. CSK6161-60
CSW6583-40Y .. CSW6593-60(Y)
CSW7571-60Y .. CSW7593-90(Y)
CSW8573-90Y .. CSW8593-140(Y)
CSW9563-140Y .. CSW95113-320(Y)
CSW10593-400Y
D
ocument for installers
Dokument für Monteure
Document pour des monteurs
ИНСТРУКЦИЯ ПО ЭКСПЛУАТАЦИИ
SB-170-9 RUS
Полугерметичные компактные винтовые компрессоры
Перевод оригинальной инструкции по эксплуатации
Русский …………………………………………………………………………………………………................. 68
Для монтажников

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Bitzer CSW7593-80Y and is the answer not in the manual?

Bitzer CSW7593-80Y Specifications

General IconGeneral
BrandBitzer
ModelCSW7593-80Y
CategoryAir Compressor
LanguageEnglish

Summary

2 Safety

2.1 Authorized staff

Work on compressors and refrigeration systems must only be performed by qualified and authorized staff.

2.2 Residual risks

Compressors may present unavoidable residual risks. Read these Operating Instructions carefully.

2.3 Safety references

Instructions to prevent hazards. Safety references must be stringently observed.

3.2 Use of flammable refrigerants of the A2 L safety group (e.g. R1234 yf)

4.3 Connecting the pipelines

4.5 Capacity control (CR) and start unloading (SU)

5 Electrical connection

5.1 Mains connections

Dimensioning motor contactors, feed lines, and fuses based on maximum operating current or power.

5.2 Motor versions

5.4 Protection devices

5.4.1 SE-E1

Standard protection device for HS, CSH, CSW compressors; monitors temperature, rotation, and phase failure.

5.4.2 CM-SW-01

5.4.3 SE-i1

5.4.4 SE-E2

5.4.5 Monitoring of the oil circuit

5.4.6 Safety devices for pressure limiting (HP and LP)

5.4.7 Oil heater

6 Commissioning

6.4 Charging refrigerant

Instructions for charging permitted refrigerants, warning about excess pressure and counterfeit refrigerants.

6.5 Checks prior to compressor start

6.6 Compressor start

6.6.1 Checking the rotation direction

Tests to confirm correct compressor rotation direction, including procedures with and without suction shut-off valve.

6.6.2 Lubricationoil level monitoring

6.6.3 Set high pressure and low pressure switches (HP + LP)

6.6.6 Checking the operating data

6.6.7 Control logic requirements

6.6.8 Particular notes on safe compressor and system operation

7 Operation

8 Maintenance

8.1 Oil change

Procedure for replacing oil, emphasizing ester oil properties, moisture sensitivity, and avoiding air penetration.

9 Decommissioning