14
SEMI-HERMETIC COMPRESSORS
Performance Data - Medium and High Temperature (R-22)
* = T for Outdoor, N for Indoor, B for Bohnmizer, S for Beacon II™
R-22 Model Compressor
Capacity BTUH @ 95°F Ambient Suction Temperature
40°F 30°F 25°F 20°F 10°F 0°F
BS*005H2 HAG-0050 5,630 4,710 4,280 3,640 2,830 –
BS*008H2 KAN-0075
8,840 7,310 6,630 5,990 4,430 –
BS*008M2
KAE-0075 – – 7,510 6,780 5,510 4,250
BS*010H2
KAR-0100 12,410 10,260 9,260 8,300 6,570 –
BS*010M2
KAM-0100 – – 9,580 8,630 6,840 5,140
BS*015H2
KAG-0150 16,340 13,350 12,230 11,000 8,770 –
BS*020H2
ERA-0200 21,310 15,900 13,700 11,500 7,220 –
BS*020M2
KAK-0200 – – 16,530 14,910 11,970 9,500
BS*021M2
ERC-0200 – – 17,640 16,010 13,000 10,430
BS*029M2
ERF-0310 – – 24,720 22,400 18,200 14,760
BS*030H2
ERF-0310 35,640 29,630 26,800 24,130 19,380 –
BS*030M2
3RA-0310 – – 32,290 29,330 23,910 19,430
BS*040H2 NRB-0400
49,860 41,700 37,830 34,160 25,000 –
BS*050H2 NRA-0500
56,500 47,720 43,310 39,360 29,700 –
BS*050M2 NRM-0500
– – 51,590 46,900 38,280 31,150
R-22 Model Compressor
Capacity BTUH @ 100°F Ambient Suction Temperature
40°F 30°F 25°F 20°F 10°F 0°F
BS*005H2 HAG-0050 5,380 4,500 4,080 3,470 2,690 –
BS*008H2 KAN-0075
8,520 7,030 6,370 5,750 4,230 –
BS*008M2
KAE-0075 – – 7,190 6,470 5,250 4,270
BS*010H2
KAR-0100 11,910 9,850 8,890 7,970 6,310 –
BS*010M2
KAM-0100 – – 9,240 8,310 6,570 4,910
BS*015H2
KAG-0150 15,690 12,820 11,740 10,560 8,420 –
BS*020H2
ERA-0200 19,300 15,000 12,900 10,800 6,540 –
BS*020M2
KAK-0200 – – 15,870 14,310 11,490 9,120
BS*021M2
ERC-0200 – – 16,930 15,370 12,480 10,010
BS*029M2
ERF-0310 – – 23,850 21,610 17,530 14,200
BS*030H2
ERF-0310 34,210 28,450 25,720 23,160 18,600 –
BS*030M2
3RA-0310 – – 31,000 28,150 22,950 18,660
BS*040H2 NRB-0400
48,150 40,240 36,480 32,810 23,900 –
BS*050H2 NRA-0500
54,570 45,950 41,820 37,850 28,400 –
BS*050M2 NRM-0500
– – 49,530 45,020 36,750 29,910
R-22 Model Compressor
Capacity BTUH @ 110°F Ambient Suction Temperature
40°F 30°F 25°F 20°F 10°F 0°F
BS*005H2 HAG-0050 4,920 4,080 3,700 3,160 2,440 –
BS*008H2 KAN-0075
7,860 6,470 5,860 5,280 3,840 –
BS*008M2
KAE-0075 – – 6,480 5,860 4,760 3,840
BS*010H2
KAR-0100 10,920 9,030 8,150 7,300 5,780 –
BS*010M2
KAM-0100 – – 8,530 7,670 6,030 4,430
BS*015H2
KAG-0150 14,380 11,750 10,760 9,680 7,720 –
BS*020H2
ERA-0200 17,200 13,400 11,500 9,540 5,510 –
BS*020M2
KAK-0200 – – 14,550 13,120 10,530 8,360
BS*021M2
ERC-0200 – – 15,520 14,090 11,440 9,180
BS*029M2
ERF-0310 – – 22,150 20,040 16,210 13,080
BS*030H2
ERF-0310 31,370 26,070 23,580 21,240 17,050 –
BS*030M2
3RA-0310 – – 28,420 25,810 21,040 17,100
BS*040H2 NRB-0400
44,540 37,140 33,660 30,330 21,900 –
BS*050H2 NRA-0500
50,440 42,210 38,540 34,690 26,100 –
BS*050M2 NRM-0500
– – 45,400 41,270 33,690 27,420
R-22 Model Compressor
Capacity BTUH @ 90°F Ambient Suction Temperature
40°F 30°F 25°F 20°F 10°F 0°F
BS*005H2 HAG-0050 5,930 4,920 4,470 3,810 2,970 –
BS*008H2 KAN-0075
9,110 7,630 6,900 6,230 4,640 –
BS*008M2
KAE-0075 – – 7,850 7,110 5,770 4,420
BS*010H2
KAR-0100 12,910 10,670 9,630 8,630 6,830 –
BS*010M2
KAM-0100 – – 9,920 8,950 7,110 5,370
BS*015H2
KAG-0150 16,990 13,880 12,720 11,440 9,120 –
BS*020H2
ERA-0200 22,270 16,800 14,500 12,300 7,970 –
BS*020M2
KAK-0200 – – 17,190 15,510 12,450 9,880
BS*021M2
ERC-0200 – – 18,350 16,650 13,520 10,850
BS*029M2
ERF-0310 – – 25,570 23,190 18,860 15,330
BS*030H2
ERF-0310 37,070 30,820 27,870 25,100 20,160 –
BS*030M2
3RA-0310 – – 33,580 30,500 24,870 20,210
BS*040H2 NRB-0400
51,530 43,040 39,170 35,390 26,300 –
BS*050H2 NRA-0500
58,700 49,500 44,950 40,860 31,000 –
BS*050M2 NRM-0500
– – 53,650 48,780 39,810 32,400