EasyManua.ls Logo

Borri INGENIO PLUS - Page 140

Borri INGENIO PLUS
203 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS user manual
Utilizzo dell’UPS
34 OMS02083 REV. A
The string on the second line may have two values, “MASTER” or “SLAVE”. Only one
MASTER UPS can be present in the system; if not there will be a conflict on the data
communication bus.
7.1.2 Parallel type
The string on the second line may have two values, “POWER” or “REDUNDANT+x”.
POWER means that the parallel system is so set as to require the presence of all the
UPS units to feed the load.
REDUNDANT+x means that the system is redundant and the redundancy index is
indicated by number “X”. For example, in a system composed of 3 UPS units,
“REDUNDANT+2” means that only one of the UPS units is sufficient to feed the load.
7.1.3 Communication bus monitoring
This menu gives a general indication regarding the communication between the UPS units
composing the system.
The numbers represent the single UPS units.
The letters M and S stand for MASTER and SLAVE respectively.
The highlighted letter indicates that we are working on that specific UPS unit.
A question mark next to a number indicates that that UPS unit is not communicating
on the data bus.
Let us assume to have the following situation:
system composed of 4 UPS units;
UPS2 is currently the MASTER UPS;
we are checking the data communication on UPS3;
UPS4 is not communicating.
The menu will be as shown below.

Related product manuals