Installation and start-up of INGENIO PLUS UPS 30÷40 kVA
Installazione e avviamento INGENIO PLUS UPS 30÷40 kVA
20 OMS02082 REV. D
3.3.1 Base plan, static load and weights
Picture 3 – Base plan
The supporting base of the UPS must be designed to carry the UPS weight and to ensure its
steady and safe support.
Its carrying capacity must be adequate to the static loads indicated in the table below.
Power (kVA) 30 40
Weight w/o batteries (kg) 120 140
Static load w/o batteries (kg/m
2
) 555 650
Weight with batteries (kg) 365 385
Static load with batteries (kg/m
2
) 1250 1350