EasyManua.ls Logo

Bosch B5512 - System Wiring Diagrams; System Wiring Overview

Bosch B5512
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Panels System wiring diagrams | en 73
Bosch Security Systems, Inc. Installation Manual 2018.07 | 16 | F.01U.287.180
18 System wiring diagrams
18.1 System wiring overview
Notice!
UL Certificated accounts
Additional power can be obtained using only a UL Listed auxiliary 12.0 VDC regulated, power-
limited power supply, such as the B520.
All terminals are power limited except BAT+ (battery positive).
All terminals are supervised except OUTPUT A, OUTPUT B, and OUTPUT C.
For proper supervision, do not loop wire under terminals. Break the wire run to provide
supervision of connections.
N/O 1
COMM
N/C 1
X1 +
X1 -
COMM
N/O 2
N/C 2
X2 +
X2 -
EOL
1
4
5
6
3
2
9
7
8
14
10
11
13
+
12
TMPR
1 COM 2 7 COM 83 COM 4 5 COM 6
RESET
ETHERNET
COM AUX
R Y G B
PWR A B COM
+ BAT -
18VAC
B C
OUTPUT
X
MODULE 1
Y
MODULE
RELEASE
NO C NC
OUTPUT A
7 COM 8
C
OUTPUT
B
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
1 k End of Line Resistors
Voltage Ranges
ON-BOARD POINTS
3.7 - 5.0 VDC
2.0 - 3.0 VDC
0.0 - 1.3 VDC
Open
Normal
Short
3 COM 4 5 COM 61 COM 2
R Y G B
SDI2
Device Bus
18 VAC
BATTERY OUTPUT A
AUX
- 12 V +
OUTPUT A
OUTPUT A
Jumper Under Cover
AUX PWR
COM
DRY
Callout á…³ Description Callout á…³ Description
1 á…³ Control panel 8 á…³ SDI2 wiring
2 á…³ UL listed class 2 transformer 18 VAC 22 VA 60
Hz (Canada: an ICP-TR1822-CA Plug-in Transformer
120 VAC primary, 18 VAC 22 VA secondary)
9 á…³ Supervised sensor loops, points 1 to 8 (Initiating
Device Circuits)
3 á…³ To earth ground 10 á…³ To ICP-EZTS Tamper Switch
4 á…³ D122/D122L, as required 11 á…³ Programmable outputs

Table of Contents

Other manuals for Bosch B5512