Control Panels Approved applications | en 93
Bosch Security Systems, Inc. Installation Manual 2018.07 | 16 | F.01U.287.180
Requirement Parameter
Supervision interval for IP and Cellular
communication is 180 seconds (ULC)
Panel Wide Parameters > Enhanced Communications > Receiver
Supervision Time set to Custom, Poll Rate set to 89, ACK Wait
Time set to 15, and Retry Count set to 5
19.8 ULC
Conduct testing monthly, with the primary de-energized.