32.4 Cross points
Points can be assigned to cross point groups. When a point in a cross
point group detects an alarm, the control panel starts the cross point
timer. If a second point in the same cross point group detects an alarm
while the cross point timer is active, the control panel sends alarm
reports for both points.
If a single cross point detects an alarm and stays in alarm throughout
the cross point timer, the control panel sends an alarm report only for
that point. If a single point in a cross point group detects an alarm and
restores while the timer is still active, the system sends an unverified
event for that point. A second alarm on the first point does not create
an alarm event, but rather an unverified event.
Cross points are:
enabled on my system.
disabled on my system.

Table of Contents

Other manuals for Bosch B8512G

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch B8512G and is the answer not in the manual?

Bosch B8512G Specifications

General IconGeneral
ModelB8512G
CategoryControl Panel
Power Supply12 VDC
SeriesG Series
Areas8
PGM Outputs on Board8
On-board EthernetYes
Wireless SupportYes
ManufacturerBosch
Input Voltage16.5 VAC
Users500
Communication FormatsIP, GSM, PSTN
CompatibilityCompatible with Bosch detectors, keypads, and communication modules