Single Stage Heat – Boiler
Example: Bosch Greenstar Gas Condensing Boilers*
Ensure the system has a C-wire
Ensure the pre-installed jumper wire remains between RH and RC
Connect the R, C and W1 wires from the boiler to R/RC, C and W/E/AUX
terminals on the wall plate, respectively
*NOTE: Bosch Greenstar boilers will require an external transformer to power the
thermostat. First remove pre-installed jumper and then connect the dry contacts
on the boiler to RH and W/E/AUX on the boiler and the transformer terminals
will connect to R/RC and C on the thermostat
Combined Single Stage Heat and Single Stage
Cool Furnace and Air Conditioner
Ensure the system has a C-wire
Remove the pre-installed jumper wire from between RH and R/RC
Connect the R, C, W1 and G wires from the Furnace to RH, C,
W/E/AUX and G terminals on the wall plate, respectively
Connect the R, C, Y1 and G wires from the Air Conditioner to R/RC, C, Y
and G terminals on the wall plate, respectively