Technical data
Climate 5000 MS – 6721830162 (2020/12)
38
8Technical data
Table 18
Outdoor unit Climate 5000 MS ... 14 OUE 18 OUE 21 OUE 27 OUE
When combined with indoor units of the type: CL3000i UW 26 E CL3000i UW 26 E CL3000i UW 26 E CL3000i UW 26 E
Cooling
Rated output kW 4.1 5.3 6.2 7.9
Rated output Btu/h 14000 18000 21000 27000
Power input at rated output W 1270 1630 1900 2440
Output (min. - max.) kW 1.4-4.8 2.3-5.6 1.9-6.7 2.2-8.5
Power input (min. - max.) W 120-1680 120-1980 125-2100 162-3250
Energy efficiency (SEER) – 6.8 6.1 6.5 6.1
Energy efficiency class – A++ A++ A++ A++
Heating
Rated output kW 4.4 5.6 6.6 8.2
Rated output Btu/h 15000 19000 22500 28000
Power input at rated output W 1185 1500 1770 2200
Output (min. - max.) kW 1.5-4.9 2.4-5.7 1.5-6.7 1.9-8.5
Power input (min. - max.) W 228-1850 240-1750 250-2000 340-2960
Energy efficiency (SCOP) at –7 °C – 4.0 4.0 4.0 4.0
Energy efficiency class at –7 °C – A+ A+ A+ A+
Energy efficiency (SCOP) at 2 °C – 5.1 5.1 5.1 5.1
Energy efficiency class at 2 °C – A+++ A+++ A+++ A+++
General
Power infeed V / Hz 220-240 / 50 220-240 / 50 220-240 / 50 220-240 / 50
Max. power consumption W 2650 2850 3300 3600
Max. current consumption A 11.5 13.0 15.5 17.5
Refrigerant – R32 R32 R32 R32
Refrigerant charge g 1100 1250 1400 1720
Design pressure MPa 4.3/1.7 4.3/1.7 4.3/1.7 4.3/1.7
Outdoor unit
Flow rate m
3
/h 2200 2200 3000 2700
Sound pressure level dB(A) 57 57 61 60
Sound power level dB(A) 65 65 65 68
Permissible ambient temperature
(cooling/heating)
°C –15...50/–15...24 –15...50/–15...24 –15...50/–15...24 –15...50/–15...24
Net weight/gross weight kg 31.8/34.9 35.5/38.5 46.8/51.1 51.1/55.8