D1255RB/D1256RB/D1257RB
|
Installation
Guide | 4.0 D1256RB Programming Requirements
.
Bosch Security Systems B.V. | 2020.03 | F01U011791-03 15
4.4.5 Keypad (Command Center) Functions
The following keypad function must be enabled
or passcode required to enable the [DETECTOR
RESET] key.
#27 Reset Sensors
Include the following items in the menu:
#9 View Event Memory
#10 View Point Status
#12 Fire Test
#21 View Log
#29 Remote Program
#32 Display Rev
Refer to Figure 18.
For the D9412GV4 v1.xx,
D9412GV3, and D9412GV2 Control
Panel, program each of the keypad
functions with
E
(enabled) and not
P
(passcode required). If
restricting any of the keypad
functions with a passcode is
required, those functions must be
executed from a custom function
that includes an authorized
passcode.
Example
(Refer to Figure 18.): If
the keypad function
View Memory
is
programmed as
P
(passcode
required), and the passcode
125600 has authority to execute it,
the keystrokes would be:
[A] [4] [0] [1] [2] [5] [6] [0] [0]
[E]
When creating a Menu Function
List for a keypad address, consider
that the D1256RB Keypad does not
have numeric keys. Ensure that:
no passcode-protected keypad
functions are in a Menu
Function List enabled at an
address that coincides with the
installed address for a
D1256RB Keypad.
the CC# Menu Key Lock prompt
is set to No for the D1256RB
address.
Figure 19: Example Keypad Functions
Keypad Functions
#
Functions
Command
E/P
1
1 Disarm ?
P
2 Master Arm Delay ? CMD 1
P
3 Master Arm Instant ? CMD 11
4 Perimeter Instant ? CMD 2
P
5 Perimeter Delay ? CMD 3
P
6 Watch Mode ? CMD 6
E
7 Perimeter Part ? CMD 8
P
Go to Main Menu
2
CMD 8
8 View Area Status ?
P
9 View Memory ? CMD 40
E
10 View Pt Status ?
E
11 Walk Test ? CMD 44
E
12 Fire Test ? CMD 58
P
13 Send Report ? CMD 41/42
P
14 Door Control ? CMD 46
P
Cycle Door ?
E
Unlock Door ?
E
Secure Door ?
E
37 Access Control Level?
P
15 Change Display ? CMD 49
E
16 Change Time/Date ? CMD 45
E
17 Change Passcode ? CMD 55
P
18 Add User ? CMD 56
P
19 Del User ? CMD 53
P
20 Extend Close ? CMD 51
P
21 View Log ?
E
22 Print Log ?
P
23 User Command 7 ? CMD 7
P
24 User Command 9 ? CMD 9
P
25 Bypass a Point ? CMD 0
P
26 Unbypass a Point ? CMD 00
P
27 Reset Sensors ? CMD 47
E
28 Change Relays ? CMD 54
P
29 Remote Program ? CMD 43
P
30 Move To Area ? CMD 50
P
32 Display Rev ? CMD 59
E
33 Service Walk ?
P
34 Default Text ? CMD 57
P
35 Change Skeds ? CMD 52
P
36 Invisible Walk ?
P
1
Keypad Function options: P = Passcode; E = Enabled
(no passcode required); Blank = Disabled