Guide | 4.0 D1256RB Programming Requirements
.
Bosch Security Systems B.V. | 2020.03 | F01U011791-03 15
4.4.5 Keypad (Command Center) Functions
The following keypad function must be enabled
or passcode required to enable the [DETECTOR
RESET] key.
• #27 Reset Sensors
Include the following items in the menu:
• #9 View Event Memory
• #10 View Point Status
• #12 Fire Test
• #21 View Log
• #29 Remote Program
• #32 Display Rev
Refer to Figure 18.
For the D9412GV4 v1.xx,
D9412GV3, and D9412GV2 Control
Panel, program each of the keypad
functions with
(enabled) and not
(passcode required). If
restricting any of the keypad
functions with a passcode is
required, those functions must be
executed from a custom function
that includes an authorized
passcode.
(Refer to Figure 18.): If
the keypad function
is
programmed as
(passcode
required), and the passcode
125600 has authority to execute it,
the keystrokes would be:
[A] [4] [0] [1] [2] [5] [6] [0] [0]
[E]
When creating a Menu Function
List for a keypad address, consider
that the D1256RB Keypad does not
have numeric keys. Ensure that:
• no passcode-protected keypad
functions are in a Menu
Function List enabled at an
address that coincides with the
installed address for a
D1256RB Keypad.
• the CC# Menu Key Lock prompt
is set to No for the D1256RB
address.
Figure 19: Example – Keypad Functions
1 Disarm ?
2 Master Arm Delay ? CMD 1
3 Master Arm Instant ? CMD 11
4 Perimeter Instant ? CMD 2
5 Perimeter Delay ? CMD 3
6 Watch Mode ? CMD 6
7 Perimeter Part ? CMD 8
Go to Main Menu
CMD 8
8 View Area Status ?
9 View Memory ? CMD 40
10 View Pt Status ?
11 Walk Test ? CMD 44
12 Fire Test ? CMD 58
13 Send Report ? CMD 41/42
14 Door Control ? CMD 46
Cycle Door ?
Unlock Door ?
Secure Door ?
37 Access Control Level?
15 Change Display ? CMD 49
16 Change Time/Date ? CMD 45
17 Change Passcode ? CMD 55
18 Add User ? CMD 56
19 Del User ? CMD 53
20 Extend Close ? CMD 51
21 View Log ?
22 Print Log ?
23 User Command 7 ? CMD 7
24 User Command 9 ? CMD 9
25 Bypass a Point ? CMD 0
26 Unbypass a Point ? CMD 00
27 Reset Sensors ? CMD 47
28 Change Relays ? CMD 54
29 Remote Program ? CMD 43
30 Move To Area ? CMD 50
32 Display Rev ? CMD 59
33 Service Walk ?
34 Default Text ? CMD 57
35 Change Skeds ? CMD 52
36 Invisible Walk ?
Keypad Function options: P = Passcode; E = Enabled
(no passcode required); Blank = Disabled
B9512G/B8512G