EN | 35
D9412G/D7412G | Operation & Installation Guide |
Bosch Security Systems | 10/03 | 43488E
Figure 13: Wiring for Installation Using the Ademco AB-12 Bell/Housing
1
2
3
4
5
6
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
LEDs Off When Normal
Charging Status
Low Battery - 12.1 VDC
YEL
RED
PROGRAMMABLE
ALARM OUTPUTS
Terminals
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
&
78
GROUND FAULT DETECT
Enabled
Disabled
PHONE
LED
RED
ON WHEN
COMMUNICATING
OFF WHEN IDLE
Digital Alarm Communicator Transmitter
Reference D9412G/D7412G Approved Application Compliance Guide (P/N:43494___)
For System Wiring Diagram, Issue A
Reference D9000/D9000G Series Technogram (P/N:33284___)
For Compatible Smoke Detectors
POWER SUPPLY REQUIREMENTS
The Power Supply Provides a Maximum of 1.4 Amps For The Control Panel and All
Accessory Devices. For System Loading, See D9412G/D7412G Operation and Installation
Guide (P/N:43488___).
All External Connections Except Terminal 5 (Battery Positive) Are Inherently Power
Limited. Requirements For Battery Standby Time May Reduce Allowable Output.
CAUTION:
See D9412G/D7412G Operation and Installation Guide (P/N:43488)
For Power Requirements Relating to Terminals 6 7
WARNING!
Multi-Battery Installation Requires
Model D122 Dual Battery Harness.
Improper Installation Can Be a Fire
Hazard.
Battery: Replace Every 3 to
5 years with Model D126, 12 V
7 Amp Hr Lead Acid Battery
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code)
and NFPA 72 (National Fire Alarm Code) for Local, Central Station, Remote Station and Household Fire
Warning Systems and under the limits of the Local Authority Having Jurisdiction (National Fire
Protection Association, Batterymarch Park, Quincy, MA 02269) Printed information describing proper
installation, operation, testing, maintenance, evacuation planning and repair service is to be provided
with this equipment.
D9412G Control / Communicator is UL Listed For Central Station, Local, Remote Station and Household
Fire Alarm, and Central Station, Local, Police Station Connect and Household Burglar Alarm.
System is Intended To Be Checked By A Qualified Technician At Least Every 3 Years.
The types of initiating circuits the panel has been approved for are A, M, W, SS.
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
GRN
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GREEN DATA BUS B
BLACK COMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 3.5
Signaling
Line
Circuits
32
31
30
29
28
27
PROG
CONN
43489G
LOOP START
PHONE MONITOR SELECT
Point 8
GND FAULT
Detect
E
N
A
B
L
E
D
I
S
A
B
L
E
ZONEX OUT 2
26
25ZONEX IN 2
ZONEX POWER +
24
ZONEX COMMON 23
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
1817 19
Point 5 Point 6
2120 22
Point 7 Point 8
GROUND START
Requires Relay
Model D136 in
Ground
Start Socket
GND START
10.2 VDC - Battery Load Shed
4
3
2
5
1
1 - Bell
2 - Inner bell box lining
3 - Outer bell box
4 - Bell tampers
5 - 220 k
0.5 W EOL
7.0 On-Board Points