DS7200V2-UK Installer's Guide Copyright 2007 Bosch Security Systems, Inc. P/N: 4998152533-02 Page 59
PART IV: CONTROL PANEL PROGRAMMING
Area Disarming (Unsetting) Options
Address: 0274
Default: 0
Selections: 0-15
Enter This Data Digit to Select Options
Area Disarming (Unsetting) Options 0 1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
No Portable ACE Disarming (Unsetting)
Portable ACE Disarms (Unsets) Area 1
Portable ACE Disarms (Unsets) Area 2
Portable ACE Disarms (Unsets) Area 3
(DS7240V2 only)
Portable ACE Disarms (Unsets) Area 4
(DS7240V2 only)
This parameter identifies to the control panel which areas are disarmed (unset) with a portable Auxiliary Control Element
(ACE). A portable ACE can be a RF keyfob or the key of a keyswitch.
One part of the confirmed alarm generation is determined by whether an area is disarmed (unset) with a portable ACE. If the
area is not disarmed with a portable ACE, opening the initial Entry door disables all means of confirmation.
This parameter only controls confirmed alarm generation. The ability to disarm (unset) with a keypad or
RF keyfob is not controlled by this parameter.
Confirmed Alarm Reset Options
Address: 0275
Default: 0
Selections: 0-15
Enter This Data Digit to Select Options
Confirmed Alarm Reset Options 0 1 2 3 4 5 6 7 8 9 10
11
12
13
14
15
Users Cannot Reset Any Confirmed Alarms
Users Can Reset Confirmed Alarms in Area 1
Users Can Reset Confirmed Alarms in Area 2
Users Can Reset Confirmed Alarms in Area 3
(DS7240V2 only)
Users Can Reset Confirmed Alarms in Area 4
(DS7240V2 only)
Use this parameter to comply with DD243 Confirmed Alarm operation. Under some configurations, a user cannot reset a
confirmed alarm. Under other configurations, a user can reset a confirmed alarm. Use this parameter to determine when a
user can or cannot reset a confirmed alarm.