Aspiration smoke detector LSN improved Planning | en 43
Bosch Sicherheitssysteme GmbH Operation guide 2020.04 | 6.1 | F.01U.029.275
– U-pipe system
6.9V fan voltage, max. 110m total pipe length
9V fan voltage, max. 110m total pipe length
– M-pipe system
6.9V fan voltage, max. 110m total pipe length
9V fan voltage, max. 160m total pipe length
– Double U-pipe system
6.9V fan voltage, max. 140m total pipe length
9V fan voltage, max. 160m total pipe length
Notice!
The sensitivity value is based on measurements with standard test fires (old value in
brackets).
I-pipe system for space protection
The diameters of the air sampling openings should be taken from the relevant table for each
pipe configuration:
1 pipe system
FAS-420-TP1
FAS-420-TT1
2 pipe systems
FAS-420-TP2
FAS-420-TT2
FAS / FCS
A
B
C D E L MF
A
B
C D E L MF
I-pipe system for space protection
I-pipe system Air sampling
opening
Number of air sampling openings
1 2 3 4 5 6 7 8 9 10 11 12 13
∅ air sampling
opening in
mm
a
A 7.0 6.0 5.2 4.6 4.2 3.8 3.6 3.4 3.0 3.0 2.5 2.5 2.5
B 6.8 5.2 4.6 4.2 3.8 3.6 3.4 3.0 3.0 2.5 2.5 2.5
C 5.6 4.6 4.4 4.0 3.8 3.4 3.2 3.0 3.0 3.0 2.5
D 5.0 4.4 4.0 3.8 3.4 3.4 3.0 3.0 3.0 2.5
E 4.4 4.2 3.8 3.6 3.6 3.4 3.0 3.0 3.0
F 4.2 3.8 3.8 3.6 3.4 3.4 3.0 3.0
G 4.0 3.8 3.6 3.6 3.4 3.2 3.0
H 4.0 3.8 3.6 3.4 3.2 3.0
I 3.8 3.6 3.6 3.2 3.2
J 3.8 3.8 3.2 3.2
K 3.8 3.8 3.4
L 4.0 3.8
M 4.0
a
Punch diameter of the aspiration reducing film sheet