EasyManua.ls Logo

Bosch Greenstar ZBR 16-3 A Series - Technical Data ZBR

Bosch Greenstar ZBR 16-3 A Series
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product Description
Greenstar – 6721822579 (2020/03)
18
3.11 Technical data ZBR...-3A
Table 3 Technical data ZBR 16-3 A..., ZBR 21-3 A...
ZBR 16-3 A... ZBR 21-3 A...
Input/Output Unit NG LPG (propane) NG LPG (propane)
Max. input rate 180/79 °F (82/26 °C) BTU/hr (kW) 57,200 (16.8) 56,400 (16.5) 79,200 (23.2) 77,500 (22.7)
Max. output rate 104/86 °F (40/30 °C) BTU/hr (kW) 54,900 (16.1) 55,300 (16.2) 74,700 (21.9) 74,700 (21.9)
Max. output rate 122/86 °F (50/30 °C) BTU/hr (kW) 54,300 (15.9) 54,600 (16.0) 74,000 (21.7) 74,000 (21.7)
Max. output rate 176/140 °F (80/60 °C) BTU/hr (kW) 50,800 (14.9) 51,200 (15.0) 70,300 (20.6) 70,300 (20.6)
Min. input rate 180/79 °F (82/26 °C) BTU/hr (kW) 12,900 (3.8) 21,500 (6.3) 24,600 (7.2) 40,100 (11.7)
Min. output rate 104/86 °F (40/30 °C) BTU/hr (kW) 12,600 (3.7) 21,500 (6.3) 23,900 (7.0) 39,900 (11.7)
Min. output rate 122/86 °F (50/30 °C) BTU/hr (kW) 12,600 (3.7) 21,500 (6.3) 23,900 (7.0) 39,600 (11.6)
Min. output rate 176/140 °F (80/60 °C) BTU/hr (kW) 11,300 (3.3) 19,400 (5.7) 21,800 (6.4) 36,200 (10.6)
Gas connection value
Natural Gas – H
s
= 1,010 BTU/ft
3
(37.3 MJ/m
3
) ft
3
/hr (m
3
/h) 56 (1.6) 78 (2.2)
Liquid Propane Gas – H
D-S
= 2,500 BTU/ft
3
(93.1 MJ/m
3
)ft
3
/hr (m
3
/h) – 22 (0.6) – 31 (0.9)
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5"
(8.7-26.1)
– 3.5-10.5"
(8.7-26.1)
LPG (propane) in. W.C. (mbar) 8-13" (19.9-32.3) 8-13" (19.9-32.3)
Flue gas
Flue gas mass flow at maximum/minimum nominal output gps 6.8/1.7 6.7/2.6 9.4/3.2 9.2/4.8
Flue gas temperature 176/140 °F (80/60 °C) at maximum/
minimum nominal heat input
°F ( °C) 136/133 (58/56) 136/133 (58/56) 145/133 (63/56) 145/133 (63/56)
Flue gas temperature 104/86 °F (40/30 °C) at maximum/
minimum nominal heat input
°F ( °C) 99/88 (37/31) 99/88 (37/31) 115/90 (46/32) 115/90 (46/32)
CO
2
at max. nominal output % 9.4 11.0 9.4 11.0
CO
2
at minimum nominal output % 8.6 10.4 8.6 10.4
Condensate
Max. condensate quantity (t
R
= 86 °F (30 °C)) gph (l/h) 0.32 (1.2) 0.32 (1.2) 0.5 (1.8) 0.5 (1.8)
pH level, approx. 4.8 4.8 4.8 4.8
General
Voltage V AC 120 120 120 120
Frequency Hz 60 60 60 60
Max. power consumption (central heating mode) W 205 205 205 205
Max. power consumption (Stand-by) W <6 <6 <6 <6
Sound pressure level dB(A) 33 33 39 39
Max. supply temperature °F ( °C) 187 (86) 187 (86) 187 (86) 187 (86)
Max. permissible operating pressure (P
MS
) heating psi (bar) 30 (2.07) 30 (2.07) 30 (2.07) 30 (2.07)
Permissible ambient temperature °F ( °C) 32 - 122 (0 - 50) 32 - 122 (0 - 50) 32 - 122 (0 - 50) 32 - 122 (0 - 50)
Nominal water capacity (heating) gal (l) 0.925 (3.5) 0.925 (3.5) 0.925 (3.5) 0.925 (3.5)
Weight (without packaging) lbs. (kg) 103.6 (47) 103.6 (47) 103.6 (47) 103.6 (47)
Dimensions, W x H x D inch
(mm)
17-21/64" × 33-15/32"13-57/64"
(440 × 850 × 353)
17-21/64" × 33-15/32"13-57/64"
(440 × 850 × 353)

Table of Contents