EasyManua.ls Logo

Bosch Greentherm T9800 SEC 199 - Page 62

Bosch Greentherm T9800 SEC 199
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 816 815 (2018/08) Greentherm T9800 SE 160/199 | SEC 199
62 | Problem solving
CE Flue blockage detected during operation due to
excessive pressure on the siphon.
Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Check exhaust pipes and terminals for obstructions
and reset the error.
Check if flue length is according to specification
(section 4.6) and reset the error.
Perform gas and air tuning ( section 8.11).
1)
CF Flue blockage detected during operation due to
insufficient combustion air.
Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Check air intake and exhaust pipes and terminals for
obstructions and reset the error.
Check if flue length is according to specification
(section 4.6) and reset the error.
Perform gas and air tuning ( section 8.11).
1)
E0 Electronic control unit internal error. Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Replace electronic control unit.
1)
E1 Hot water temperature above 194 °F.
Appliance burner cut off to prevent scalding and
reactivation after cooling down.
Disconnect the appliance and purge hydraulic
circuit to remove air.
If the problem persists:
Reduce setpoint temperature to minimize
temperature instabilities.
E3 Flue gases temperature above 167 °F (residential)
/ 194 °F (commercial) or 2 minutes above 145 °F.
Appliance burner cut off to prevent overheating.
Descale appliance ( section 7.3).
1)
Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Check sensor resistance [15] (section 11) and
replace the sensor if it is not according to
specification.
1)2)
E4 Air temperature inside cabinet above 176 °F or 2
minutes above 158 °F.
Appliance burner cut off to prevent overheating.
Check for flue gas leakage inside the cabinet or
concentric vent.
1)
Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Check sensor resistance [18] (section 11) and
replace the sensor if it is not according to
specification.
1)
2)
E5 Condensing unit flue gases temperature above
428 °F or 2 minutes above 392 °F.
Appliance burner cut off to prevent overheating.
Descale appliance ( section 7.3).
1)
Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
Check sensor resistance [16] (section 11) and
replace the sensor if it is not according to
specification.
1)
2)
Display Description Solution
Table 27

Table of Contents

Related product manuals