SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
Models Covered
by This Manual:
ThroughTheWall Models:
RC2PV50H*(N,X)
LC2PV50H76*(N,X)
(*) Denotes Warranty Years
Through-The-Wall Gas Water Heaters
Condensing PV Series
http://waterheatertimer.org/power-vent-water-heater-troubleshoot.html

Questions and Answers

  • C
    Christopher OdomAug 13, 2025
    What causes a Bradford White LC2PV50H76N Water Heater pilot flame to be extinguished?
    • A
      Anita HawkinsAug 13, 2025
      If the pilot flame is extinguished and the system auto-resets, the possible causes are: unstable pilot, blocked or restricted pilot tube, oxidation build-up on the pilot electrode, wire damage to the pilot assembly or a bad connection at the gas valve, insufficient combustion air, or gas pressure out of specification.
  • M
    Michael BurkeAug 16, 2025
    Why does my Bradford White LC2PV50H76N Water Heater fail to light the pilot and auto reset?
    • T
      Travis WarrenAug 17, 2025
      If the pilot fails to light and the system auto-resets, this could be due to an unstable pilot, a blocked or restricted pilot tube, oxidation build-up on the pilot electrode, wire damage to the pilot assembly or a bad connection at the gas valve, or low gas pressure.
  • N
    Nathan TaylorAug 20, 2025
    What causes a Bradford White LC2PV50H76N Water Heater to sense an undesired false pilot flame?
    • P
      Patrick GriffinAug 20, 2025
      An undesired false pilot flame sensed in your Bradford White water heater, causing the system to auto-reset, is likely due to the pilot valve being stuck in the open position. Replace the gas control.
  • K
    Kevin YatesAug 25, 2025
    What causes a gas valve fault to be detected in a Bradford White Water Heater?
    • B
      Brenda OlsonAug 25, 2025
      If a gas valve fault is detected, this could be because the control needs to be reset or the control is wet or physically damaged. To reset, interrupt the power supply. If the control is wet or damaged, replace the gas control.
  • K
    Kelli WeissAug 28, 2025
    What does it mean if my Bradford White LC2PV50H76N detects a gas valve electronics fault?
    • A
      Annette JohnsonAug 28, 2025
      If a gas valve electronics fault is detected, it could mean that the control needs to be reset or that the control is wet or physically damaged. To reset it, interrupt the power supply. If the control is wet or damaged, replace the gas control.
  • K
    Kenneth LeeSep 1, 2025
    What causes a Temperature Sensor fault in Bradford White Water Heater?
    • M
      Matthew SchwartzSep 1, 2025
      A temperature sensor fault may be caused by damage to the temperature sensor wire or the temperature sensor resistance being out of range.
  • T
    Thomas SextonSep 4, 2025
    What does it mean if my Bradford White LC2PV50H76N Water Heater detects a Simulated Resistive Device out of specification?
    • P
      Philip LandrySep 5, 2025
      A 'Simulated Resistive Device out of specification' error indicates that the simulated resistive device is out of specification, possibly due to a short.
  • T
    Thomas CarterSep 8, 2025
    What does it mean if my Bradford White LC2PV50H76N Water Heater detects a Simulated Resistive Device fault?
    • K
      kclaySep 9, 2025