S19-2200
EFX 60/S19-2200
Thermostatic Mixing Valve
with Optional Cabinet
Robinet thermostatique mélangeur
avec armoire en option
Válvula mezcladora termostática con
armario opcional
Inlet Connections: 1" NPT
Outlet Connection: 1-1/4" NPT
Temperature Range: 65 95°F
Maximum Pressure: 125 PSI
Inlet Temperature Hot: 120 180° F
Inlet Temperature Cold: 33 80° F
Minimum Temperature Differential
(from valve set point): 20° F
Raccords d’arrivée : 1 po NPT
Raccord de sortie : 1-1/4 po NPT
Plage de température : 65 95 °F
Pression maximum : 125 lb/po
2
Température d’arrivée, eau chaude : 120 180 °F
Température d’arrivée, eau froide : 33 80 °F
Différence de température minimum
(à partir de valeur de consigne de robinet) : 20 °F
Conexiones de entrada: NPT de 1 pulg.
Conexión de salida: NPT de 1-1/4 pulg.
Rango de temperaturas: 65 – 95 °F
Presión máxima: 125 PSI
Temperatura de entrada, caliente: 120 – 180 °F
Temperatura de entrada, fría: 33 – 80 °F
Diferencial de temperatura mínima
(desde el punto de ajuste de la válvula): 20 °F
EFX60/P/RS
Table of Contents
Supplies recommended for installation ...........................................3
Tools required for temperature adjustment .....................................3
Install Optional Cabinet ...................................................................3
Connect Supply Lines and Install Thermometer .............................5
Adjust Temperature with Water Running .........................................5
Test Unit ..........................................................................................5
Optional Water Recirculation Setup ................................................6
Troubleshooting Thermostatic Mixing Valve ....................................7
Troubleshooting: Piston Disassembly and Cleaning .......................8
Parts Breakdown .............................................................................9
Sommaire
Fournitures requises pour l’installation :........................................11
Outils requis pour réglage de température ...................................11
Installer l’armoire en option. ..........................................................11
Connecter les conduites d’alimentation et installer le thermostat .13
Régler la température avec l’eau qui s’écoule ..............................13
Tester unité .................................................................................... 13
Configuration de recirculation d’eau optionnelle ...........................14
Dépannage du robinet mélangeur thermostatique .......................15
Dépannage : Démontage du piston et nettoyage .........................16
Liste des pièces ............................................................................17
Tabla de contenidos
Materiales recomendados para la instalación...............................19
Herramientas necesarias para el ajuste de temperatura ..............19
Instale el gabinete opcional ..........................................................19
Conecte las tuberías de suministro e instale el termómetro ........21
Ajuste la temperatura con el agua corriendo ................................21
Unidad de prueba .........................................................................21
Instalación de recirculación opcional de agua ..............................22
Solución de problemas de la válvula mezcladora termostática ....23
Solución de problemas: Desensamble y limpieza del pistón ........24
Desglose de piezas ....................................................................... 25

Other manuals for Bradley S19-2200

Questions and Answers

  • M
    Michael WatsonAug 3, 2025
    Why is the water temperature fluctuating on my Bradley Control Unit?
    • J
      Justin AllenAug 4, 2025
      If you're experiencing temperature fluctuations or improper temperature with your Bradley Control Unit, several factors could be the cause. The stop and check sections of the valve may not be moving freely, or the thermostat could be slowly failing. Clean the stop and check valves, or check/replace the thermostat. Another cause may be that the inlet supply line to the mixing valve is being shared by other equipment, reducing the inlet pressure. In this case, enlarge the supply line size, reconfigure the supply line, or regulate the supply usage. Also, the recirculation may not be balanced. Finally, the piston may not move freely and must be cleaned.
  • B
    Brandon OchoaAug 11, 2025
    What to do if my Bradley Control Unit has limited water flow?
    • E
      Edward RodriguezAug 12, 2025
      If you're experiencing limited water flow from your Bradley Control Unit, it could be due to a couple of reasons. The inlet shut-off valve may be partially closed, or there could be a significant decrease in water pressure. Also, dirt and debris may have collected on the check screen or seat, limiting the movement of the stop and checks. To resolve this, remove the stop and checks, clean the screen and seat, and reassemble the valve. The components may be scraped with a screwdriver to remove debris, and tweezers can be used to pull debris out from the seat. If the stop and checks need replacement, contact your Bradley representative and ask for Check/Stop Kit (S65-179).
  • S
    Sharon SawyerAug 18, 2025
    How to fix no hot water flow in Bradley S19-2200 Control Unit?
    • J
      Jennifer MendozaAug 18, 2025
      If your Bradley Control Unit is only dispensing cold water, it's likely that the thermostat has failed, which has subsequently engaged the safety shut-off. To check this, remove the top cap and pull out the push rod and thermostat. Insert a 7/16" dia. rod into the thermostat bellows. Mark the length of the thermostat bellows (at room temperature, with 10 lb. of force, the bellows length should be approx. 2-5/8\"). If the thermostat bellows length is not in the proper range, the thermostat must be replaced (it cannot be repaired). Contact your Bradley representative and ask for Thermostat Kit (S65-178).
  • L
    Latasha GonzalezAug 26, 2025
    How to stop external leaks in Bradley S19-2200 Control Unit system?
    • O
      Omar JonesAug 26, 2025
      If you notice external leaks in your Bradley Control Unit system, it's likely that either the NPT joints or the o-rings have been damaged. Replace the NPT joints and/or o-rings where necessary. For replacement of o-rings, contact your Bradley representative and ask for O-Ring Seal Kit (S65-177).

Summary

Installation Procedures

Install Optional Cabinet

Guide for installing the optional recessed or surface-mounted cabinet.

Connect Supply Lines and Install Thermometer

Steps for connecting water supply lines and installing the thermometer.

Adjust Temperature with Water Running

Procedure for adjusting water temperature during operation.

Test Unit

Instructions for testing the proper function of the mixing valve.

Optional Water Recirculation Setup

Instructions for configuring the optional water recirculation system.

Troubleshooting Guide

Thermostatic Mixing Valve Issues

Common problems and solutions for the thermostatic mixing valve.

Piston Disassembly and Cleaning

Detailed procedure for cleaning and disassembling the valve piston.

Parts Breakdown

Bradley S19-2200 Specifications

General IconGeneral
BrandBradley
ModelS19-2200
CategoryControl Unit
LanguageEnglish