EasyManua.ls Logo

Brainchild BTC-9300 - 5-4 Cool Only Control

Brainchild BTC-9300
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UM93001D
5 4 Cool Only Control5 4 Cool Only Control
A BTC-9300 is used to control a refrigerator at temperature below 0 C. To
avoid the set point adjustment beyond the interesting range, SP1L is set at -
10 C and SP1H is set at 0 C. The temperature is lower than the ambient, a
cooling action is required. Hence select DIRT for OUT1. Since output 1 is used
to drive a magnetic contactor, O1TY selects RELY. A small temperature
oscillation is tolerable, hence use ON-OFF control to reduce the over-all cost.
To achieve ON-OFF control, PB1 is set with zero and O1HY is set at 0.1 C.
B
BB
B
A BTC-9300 is used to control a refrigerator at temperature below 0C.To
avoid
the set point adjustment beyond the interesting range, SP1L is set at -
10 C
and SP1H is set at 0C.The temperature is lower than the ambient, a
cooling
action is required. Hence select DIRT for OUT1. Since output 1 is used
to
drive a magnetic contactor, O1TY selects RELY. A small temperature
oscillation
is tolerable, hence use ON-OFF control to reduce the over-all cost.
To
achieve ON-OFF control, PB1 is set with zero and O1HY is set at 0.1 C.
B
BB
B
Setup Summary:Setup Summary:
FUNC=BASC
IN1=PT.DN
IN1U= C
DP1=1-DP
OUT1=DIRT
O1TY=RELY
SP1L=-10 C
SP1H= 0 C
FUNC=BASC
IN1=PT.DN
IN1U=
C
DP1=1-DP
OUT1=DIRT
O1TY=RELY
SP1L=-10
C
SP1H=
0 C
User Menu:User Menu:
PB1=0 ( C )
O1HY=0.1 ( C )
PB1=0 ( C )
O1HY=0.1
( C )
Cooling Control ExampleCooling Control Example
A1 A2 PV
C
SV
OUT
BTC-9300
Figure 5.6Figure 5.6
RTD
Refrigerator
11 12
13
5
6
Mains
Supply
Mains
Supply
87
ON-OFF control
Direct Control Action
ON-OFF control
Direct
Control Action

Table of Contents

Related product manuals