Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
49
Cooler Operation:
(cont.)
N-E5 Electronic Control Module Operation:
(cont.)
The N-E5 controller is fitted with an internal 8 Amp fuse to protect the PCB circuitry.
The 8 Amp fuse will protect the N-E5 controller from short circuit and/or high current
draw, on the following circuits:
Pump
Water inlet solenoid
Fan motor
PCB relays
Important Note:
The N-E5 internal 8 Amp fuse does not protect the control against short circuit on the
ServoSeal / drain valve motor circuit.
The N-E5 controller will maintain a minimum voltage on the output to the water inlet
solenoid in the OFF cycle.