Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
95
Dealing with Problem Installations
(cont.)
Water Entering Building
When dealing with the problem of water entry in a building, it is often difficult to
ascertain the water source, due to water tracking and capillary action.
The following checks relate to both Cooler faults and installation faults:
Check the Cooler's base and trough is not damaged.
Check the Cooler is installed level and the overflow pipe can function correctly.
Check the water distribution system is not blocked causing incorrect / excessive
water to pads or water tracking.
Check the operation of the filter pads and ensure there is no water lift off.
Check the flashing of the dropper duct, water supply pipe, electrical conduits and
drain pipes for leakage.
Check internal water pipe and drain pipe lines and fittings for leakage.
Check the roof (tiles etc.) for damage.
Check for any sign of water/moisture, on the inside of the ductwork and bell
housing.
Check the route of any water discharge from the Cooler i.e. roof guttering and
water run off area down stream of Cooler.