Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
61
Cooler Operation
(cont.)
Pump Operation
(cont.)
Pump will not operate
Check that the pump is switched ON and that the pump is not in an operation
delay period i.e. water contact across Trident probes or Servoseal open time.
Check for 240 Volt output to the pump, at the PUMP-NEUTRAL and PUMP-
ACTIVE terminals on the pump.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
Multimeter
240
PUMP - NEUTRAL
PUMP - ACTIVE