Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
72
Cooler Operation
(cont.)
ServoSeal and Drain Valve Operation
(cont.)
Dismantling
ServoSeal / Drain Valve Motor (only) removal:
Isolate the 240 Volt power supply (N-E5).
Open service access compartment cover.
Disconnect the ServoSeal / drain valve motor wiring loom.
Remove the motor retaining clip holding the motor onto the gear linkage
mechanism.
Retract the motor.
With the motor removed the gear linkage mechanism action can be manually
operated and checked.
Motor and gear linkage mechanism removal:
Remove the drain valve level set screw and release the level from the geared cam
shaft.
Remove the fan impeller from the fan motor shaft, to gain access to ServoSeal
louver linkages (refer to fan dismantling procedures).
Remove the 2 linkage retaining screws that hold the lower linkage arm onto the
ServoSeal louver coupling.
Remove the 3 screw retaining the gear linkage mechanism to the service
compartment back wall.
Manoeuvre the linkage arms through the service compartment back wall opening,
and remove assembly.
Disconnect motor cam lever switch.
Disconnect linkage arm and cam shaft.