Brooks ALARM 2000 - Fault Test; System off Test; Sprinkler Module Testing

Brooks ALARM 2000
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Site Manual
Alarm 2000 Iss 5
37
2. Simulate activation of the Manual Call Point (if fitted)
The MCP Alarm Activated” LED flashes
Monitored 24V
DC
alarm output is switched on (Bell ringing if fitted)
Any other facility connected to the alarm bus will activate
3. Activate the “Panic Input”, the system activates the Fire Mode as per step1
4. Go to any Smoke / Heat Alarm press and hold the test button, all the Smoke or
Heat Alarms will sound. With the test button still pressed and the Smoke / Heat
Alarm still sounding press the Alarm Locate switch. All the Smoke / Heat Alarms
should stop sounding except the unit with the test button pressed. The Locate
facility should be active for approximately 5 minutes. To cancel the five minutes
timer, turn the key switch to “Off” position then press and hold the Locate button
until the amber LED in the switch body distinguish.
Repeat step 4 by pressing the Alarm Isolate” switch (if the Smoke / Heat Alarms are wired
as a 4-wire system) instead of “Alarm Locate, all the Smoke or Heat Alarms will be
disabled for approximately 5 minutes including the Smoke Alarm that has been activated.
5.5.3.2 Fault Test:
1. Remove EOL Resistor of the MCP
MCP Fault LED illuminates
Fault sounder is sounding
Common fault relay is energised
Press Sounder Silence button, the fault sounder will mute.
2. Remove EOL Resistor of the monitored alarm output
Alarm Output Fault LED illuminates
Fault sounder is sounding
Common fault relay is energised
Press Sounder Silence button, the fault sounder will mute.
5.5.3.3 System Off Test:
Turn the key switch to “OFF position
System Off red LED (rectangular) will be flashing
System OFF relay is energised
5.5.3.4 Sprinkler Module Testing:
1. Simulate Sprinkler alarm input by bridging sprinkler input terminals (SPK/IN)
Sprinkler Activated” red LED flashes
Monitored 24V
DC
Sprinkler alarm output is activated
Sprinkler alarm relay is energised
Note: If the Sprinkler alarm is required to activate all the Smoke / Heat Alarms, a
normally open Sprinkler alarm relay contact must be connected to the Panic input
in the Main Control board.
2. Simulate Monitored Valve alarm input by bridging the Monitored Valve input
terminals (MV/IN)
Monitored Valve Tamper red LED flashes
Monitored 24V
DC
Monitored Valve alarm output is activated if the output is
not disabled
Sprinkler alarm relay is energised