Site Manual
Alarm 2000 Iss 5
47
Tick the relevant boxes
INSTRUCTIONS
1. Is this report a supplementary to a previous commissioning report?
Yes No Not applicable
2. Is the following documentation available?
(a) Operators manual Yes No Not applicable
(b) Installer’s statement Yes No Not applicable
(c) ‘As installed’ drawings Yes No Not applicable
(d) Previous Com. Reports Yes No Not applicable
SYSTEM INFORMATION
Basic Configuration
3. Check that the control panel is suitably located and secured against tampering
Yes No Not Applicable
4. Ensure control panel is configured as per the installer’s statement
Yes No Not Applicable
5. Ensure that all Smoke and Heat Alarms are:
(a) Listed in the installer’s statement Yes No Not Applicable
(b) Compatible with the control panel Yes No Not Applicable
(c) Installed in an environment for Yes No Not Applicable
which they are suited.
6. Ensure that all ancillary equipment is
(a) Listed in the installer’s statement Yes No Not Applicable
(b) Compatible with the control panel Yes No Not Applicable
(c) Installed in an environment for Yes No Not Applicable
which they are suited.
7. Check that the primary power source for the system has been provided in
accordance with AS3000 or TS009 as appropriate, and that the isolating switch
disconnects the active conductors.
Yes No Not Applicable