Table 14 — Damper Position Control, 2-Speed Fan Motor, Economizer Cooling Not Available
INPUT VOLTAGE
OCC 0-V 24-V 24-V 24-V 24-V
Y1 0-V 0-V 24-V 24-V 0-V
Y2 0-V 0-V 0-V 24-V 0-V
W1 0-V 0-V 0-V 0-V 24-V
SUPPLY FAN MOTOR SPEED
SUPPLY FAN
MOTOR SPEED
OFF LOW LOW HIGH HIGH
DAMPER POSITION
No CO
2
Sensor CLOSED MIN POS-L MIN POS-L MIN POS-H MIN POS-H
W/ CO
2
Sensor CLOSED
FROM VENTMIN L TO
VENTMAX L
FROM VENTMIN L TO
VENTMAX L
FROM VENTMIN H
TO
VENTMAX H
FROM VENTMIN H
TO
VENTMAX H