—14—
PERFORMANCE DATA (CONT)–STANDARD ECM INDOOR MOTOR
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE -10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
604B042 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
1100/0.06 1225/0.07 1400/0.08
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75
TC 39.6 40.4 43.4 47.6 40.5 41.2 44.2 48.4 41.5 42.1 45.1 49.4
SHC 33.5 27.6 28.6 23.4 35.4 29.0 30.0 24.3 37.9 30.8 31.9 25.6
kW 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.1
85
TC 37.9 38.7 41.5 45.5 38.7 39.4 42.3 46.3 39.7 40.2 43.2 47.2
SHC 32.8 26.9 27.8 22.7 34.6 28.2 29.2 23.6 37.0 30.0 31.1 24.8
kW 3.3 3.3 3.4 3.4 3.3 3.3 3.4 3.4 3.3 3.3 3.4 3.4
95
TC 36.2 36.8 39.6 43.4 36.9 37.5 40.3 44.1 37.8 38.2 41.0 44.9
SHC 32.0 26.1 27.0 21.9 33.8 27.4 28.4 22.8 35.9 29.1 30.3 24.0
kW 3.7 3.7 3.7 3.8 3.7 3.7 3.7 3.8 3.7 3.7 3.7 3.8
105
TC 34.2 34.8 37.4 41.0 34.9 35.4 38.0 41.6 36.0 36.0 38.7 42.3
SHC 31.0 25.2 26.2 21.1 32.7 26.5 27.6 22.0 34.3 28.3 29.4 23.2
kW 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1
115
TC 32.1 32.6 35.0 38.4 32.8 33.1 35.5 38.9 34.0 33.7 36.1 39.5
SHC 30.0 24.3 25.2 20.2 31.4 25.6 26.6 21.0 32.8 27.3 28.5 22.2
kW 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.6
125
TC 29.8 30.1 32.3 35.3 30.6 30.5 32.7 35.7 31.7 31.0 33.2 36.2
SHC 28.6 23.2 24.2 19.1 29.6 24.5 25.5 20.0 30.6 26.1 27.3 21.1
kW 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0
604B042
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-10 0 10 17 20
60
1225
TC
13.6
12.5 16.6 15.3 19.7 18.1 22.2 20.2 23.7 21.5
kW
2.42 2.51 2.64
2.76 2.81
1400
TC
13.6
12.6 16.7 15.3 19.8 18.2 22.3 20.3 23.7 21.5
kW
2.39 2.48 2.60 2.70 2.75
1575
TC
13.7
12.7 16.8 15.5 19.8 18.2 22.3 20.4 23.8 21.6
kW
2.36 2.24 2.54 2.63 2.68
70
1225
TC
13.0
12.1 16.1 14.9 19.4 17.8 21.8 19.9 23.3 21.1
kW
2.70 2.80 2.93
3.05 3.11
1400
TC
13.2
12.2 16.2 14.9 19.4 17.8 21.9 20.0 23.4 21.2
kW
2.67 2.76 2.88 2.99 3.05
1575
TC
13.2
12.2 16.3 15.0 19.5 17.9 22.0 20.1 23.5 21.3
kW
2.64 2.72 2.82 2.93 2.98
80
1225
TC
12.8
11.9 16.0 14.7 19.0 17.4 21.4 19.6 22.9 20.8
kW
3.02 3.13 3.25
3.37 3.43
1400
TC
12.9
11.9 15.9 14.6 19.0 17.4 21.5 19.6 23.0 20.9
kW
2.99 2.97 2.83 3.31 3.37
1575
TC
13.0
12.0 15.8 14.6 19.1 17.6 21.6 19.7 23.1 21.0
kW
2.96 3.04 3.14 3.24 3.30
604B042
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30 40 47 50 60
60
1225
TC
29.2
25.6 35.6 35.6 40.8 40.8 42.0 42.0 49.8 49.8
kW
2.99 3.20 3.35
3.40 3.70
1400
TC
29.3
25.7 35.8 35.8 41.0 41.0 43.0 43.0 50.2 50.2
kW
2.91 3.09 3.24 3.31 3.55
1575
TC
29.4
25.8 36.0 36.0 41.3 41.3 43.2 43.2 50.6 50.6
kW
2.82 2.99 3.13 3.18 3.41
70
1225
TC
28.8
25.2 35.1 35.1 40.1 40.1 41.9 41.9 48.8 48.8
kW
3.32 3.57 3.74
3.81 4.11
1400
TC
28.9
25.3 35.3 35.3 40.3 40.3 42.1 42.1 49.1 49.1
kW
3.24 3.46 3.62 3.68 3.95
1575
TC
29.0
25.4 35.4 35.4 40.5 40.5 42.4 42.4 49.5 49.5
kW
3.16 3.35 3.49 3.56 3.79
80
1225
TC
28.4
24.9 34.6 34.6 39.5 39.5 41.3 41.3 47.9 47.9
kW
3.68 3.97 4.14
4.22 4.55
1400
TC
28.5
25.0 34.7 34.7 39.7 39.7 41.5 41.5 48.2 48.2
kW
3.59 3.85 4.01 4.08 4.38
1575
TC
28.6
25.1 34.9 34.9 39.9 39.9 41.7 41.7 48.6 48.6
kW
3.51 3.73 3.88 3.94 4.21