Fig. 38 -- Example of Single Stage Furnace Control
Table 11 Electrical Data
FURNACE SIZE
V O LT S ---
H E R T Z ---
PHASE
OPERATING VOLTAGE
RANGE*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXI-
MUM
WIRE
LENGTH
FT (M)}
MAXIMUM
FUSE OR CKT
BKR AMPS
Maximum* Minimum*
30040E14 1 1 5 --- 6 0 --- 1 127 104 7.1 9.8 14 37 (11.5) 15
36040E17 1 1 5 --- 6 0 --- 1 127 104 7.1 9.8 14 37 (11.5) 15
36060E14 1 1 5 --- 6 0 --- 1 127 104 7.2 9.9 14 37 (11.4) 15
42060E17 1 1 5 --- 6 0 --- 1 127 104 7.2 9.9 14 37 (11.4) 15
48080E17 1 1 5 --- 6 0 --- 1 127 104 7.2 9.9 14 37 (11.4) 15
60080E21 1 1 5 --- 6 0 --- 1 127 104 9.6 12.9 14 28 (8.7) 15
60100E21 1 1 5 --- 6 0 --- 1 127 104 9.7 13.0 14 28 (8.7) 15
60120E24 1 1 5 --- 6 0 --- 1 127 104 9.7 13.0 14 28 (8.7) 15
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,
etc.) full load amps.
{Time---delay type is recommended.
}Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.