57
Avoid short horizontal osets with 90
deg. Elbows. Short osets can be
dicult to slope and may trap con-
densate.
Use 45 deg. Elbows where
possible, to ensure conden-
sate drainage.
Slope vent pipe back to the
furnace at least ¼” per foot
A14546
Fig. 42 Near Furnace Vent Connections
FURNACE
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
NOT IN
HORIZONTAL
SECTION
A93034
Fig. 43 Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration
Clearance distances for
items greater than 3 feet
(1 meter ) away from the
inside corner, refer to the
Inside Corner Clearance
Table.
No operable windows, doors or
intakes of any type within the
shaded areas of Wall A and B.
For all other items, refer to the Inside
Corner Clearance Table.
3 ft. (1 M) to
6 ft. (2 M)
Notes:
For this illustration, Wall A is the wall adjacent to the wall the
vent termination is located. Wall B is the wall the vent
termination is located.
The termination can be located on either wall.
Minimum distance of a vent terminal to an inside corner is
3 ft. (1 M).
Maximum distance from an inside corner is 6 ft. (2 M).
If the vent termination is located more than 6 ft. (2 M) away
from an inside corner, refer to the appropriate Direct or
Non−Direct Vent Clearance Tables.
Vent
Termination
3 ft. (1 M)
V
A170005
Fig. 44 Inside Corner Termination
986TB