90
Is AMBER LED status light on?
Is there 24V at SEC-1 and SEC-2?
Is there 115V at L1 and L2?
Replace furnace control.
Is door switch closed?
Replace transformer.
Replace door switch.
Is there 115V going to switch?
Is door switch closed?
Is circuit breaker closed?
Check for continuity in wire from circuit
breaker to furnace.
Close circuit breaker and go back to
START.
Is AMBER LED status light blinking
rapidly without a pause?
Check for correct line voltage polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
Is AMBER LED status light blinking
ON/OFF slowly with a combination of
short and long ashes?
Determine status code. The status code
is a 2 digit number with the rst digit
determined by the number of short
ashes and the second digit by the
number o ong ashes?
To recall previous status codes disconnect the R
thermostat connection, reset power, and put setup
switch SW1-1 in the ON position. The AMBER LED
will ash the status codes in the order of occurrence.
Record status codes until status code #11 ashes (1
short and 1 long ash). After status code #11
ashes the status codes will repeat. Status codes
are erased after 72 hours or can be manually erased
by putting setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2 simultaneously
until status code #11 is ashed. When done put
setup switch SW1-1 in the OFF position.
Was there a previous status code other
than #11?
Go to section below for the status code
that was ashed.
Does the control respond to W/W1, W2,
Y1, Y/Y2, and G (24V) thermostat
signals?
Run system through a low-heat, high-
heat, or cooling cycle to check operation.
Status codes are erased after 72 hours
or can be manually erased by putting
setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2
simultaneously until status code #11 is
ashed.
Is 24V present at W/W1, W2, Y1, Y/Y2 or
G thermostat terminals on the furnace
control?
Check room thermostat or
interconnecting cable.
Disconnect all the thermostat wires from
the furnace control.
Does the problem repeat when using a
jumper wire?
Replace furnace control.
The thermostat is not compatible with the
furnace control. Either install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
YES
NO
YES
YES
YES
YES
YES
SEYSEYSEY
YES
START
YES
YES
NO
NO
NO
ONON
NO
ONON
NO
NO
NO
roubleshootin
Guide
A11326A
Fig. 72 − Troubleshooting Guide
986TB