EasyManuals Logo

Bryant Legacy Series Installation Instructions

Bryant Legacy Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
2
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in serious personal
injury, death, and/or property damage.
Disconnect gas piping from unit when leak testing at pressure
greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig
(3450 Pa) will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig (3450 Pa), it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
0.5 psig (3450 Pa) or less, a unit connected to such piping must
be isolated by closing the manual gas valve(s).
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
This system uses Puron
®
refrigerant, which has higher pres-
sures than R-22 and other refrigerants. No other refrigerant
may be used in this system. Gage set, hoses, and recovery
system must be designed to handle Puron refrigerant. If un-
sure about equipment, consult the equipment manufacturer.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or
death.
Relieve pressure and recover all refrigerant before system re-
pair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger-
ants and oils.
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing
materials.
Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.
WARNING
CARBON-MONOXIDE POISONING HAZARD
Failure to follow instructions could result in severe personal
injury or death due to carbon-monoxide poisoning, if combus-
tion products infiltrate into the building.
Check that all openings in the outside wall around the vent
(and air intake) pipe(s) are sealed to prevent infiltration of
combustion products into the building.
Check that furnace vent (and air intake) terminal(s) are not ob-
structed in any way during all seasons.
AVERTISSEMENT
RISQUE D’INTOXICATION AU MONOXYDE DE
CARBONE
Si ces directives ne sont pas suivies, cela peut entraîner des
blessures graves ou une intoxication au monoxyde de carbone
pouvant causer la mort, si des produits de combustion
s’infiltrent dans le bâtiment.
Vérifier que toutes les ouvertures pratiquées dans le mur
extérieur autour du ou des tuyaux d’évent (et de la prise d’air)
sont scellées de manière à empêcher l’infiltration de produits
de combustion dans le bâtiment.
Veiller à ce que la ou les sorties de l’évent de l’appareil de
chauffage (et la prise d’air) ne soient, en aucune façon,
obstruées, quelle que soit la saison.
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Inlet pressure tap set screw must be tightened and
1
/
8
-in. NPT
pipe plug must be installed to prevent gas leaks.
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Manifold pressure tap set screw must be tightened and
1
/
8
-in.
NPT pipe plug must be installed to prevent gas leaks.
GAS VALVE
INLET PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW

Other manuals for Bryant Legacy Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant Legacy Series and is the answer not in the manual?

Bryant Legacy Series Specifications

General IconGeneral
Cooling Capacity1.5 to 5 tons
SeriesLegacy Series
Compressor TypeSingle-Stage
RefrigerantR-410A
Warranty10-year parts limited warranty upon timely registration

Related product manuals