EasyManua.ls Logo

Bryant Plus 90i - Performing Routine Maintenance; Shutting down Your Furnace; Filtering out Trouble

Bryant Plus 90i
13 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
A86035
degrees
at
the
top
of
your
thermostat
“comfort
level”
are
the
most
costly
degrees
to
obtain.
When
the
room
temperature
drops
below
the
temperature
selected
on
the
thermostat,
the
furnace
will
be
switched
on
automatically.
When
the
room
temperature
reaches
the
degree
selected
on
the
thermostat,
the
furnace
will
be
au¬
tomatically
switched
off.
Some
thermostats
have
a
“fan”
switch
with
2
selections:
AUTO
or
ON.
When
set
on
AUTO,
the
furnace
blower
cy¬
cles
on
and
off,
controlled
by
the
thermostat.
In
the
ON
position,
the
furnace
blower
runs
continuously.
This
keeps
the
temperature
level
in
your
home
more
evenly
bal¬
anced.
It
also
continuously
filters
the
indoor
air.
SHUTTING
DOWN
YOUR
FURNACE
Should
you
need
to
shut
down
your
furnace
for
service
or
main¬
tenance,
you
will
need
to
turn
the
furnace
OFF.
The
following
procedures
must
be
followed:
1.
Set
your
room
thermostat
to
the
lowest
temperature
set¬
ting.
(See
Fig.
18.)
2.
Close
the
external
manual
gas
valve.
(See
Fig.
9.)
5.
Thrn
the
control
knob
on
the
gas
valve
to
the
OFF
position.
(See
Fig.
20.)
6.
Replace
the
control
access
door.
(See
Fig.
14
or
15.)
7.
If
the
furnace
is
being
shut
down
because
of
a
malfunction,
call
your
dealer
as
soon
as
possible.
20
A87374
-uring
winter.
(See
winterising
procedures
in
mainte-
PERFORMING
ROUTINE
MAINTENANCE
With
proper
maintenance
and
care,
your
furnace
will
operate
economically
and
dependably.
Instructions
for
basic
mainte¬
nance,
which
can
easily
be
followed,
are
found
on
this
and
the
following
pages.
However,
before
beginning
maintenance,
fol¬
low
these
safety
precautions:
FILTERING
OUT
TROUBLE
A
dirty
filter
will
cause
a
loss
of
airflow
in
your
duct
system;
the
microprocessor
will
detect
an
airflow
change
and
compensate
for
slight
variations.
When
the
microprocessor
cannot
compen¬
sate
for
the
excessive
loss
of
airflow,
a
blower
calibration
fault
will
be
signaled
and
the
furnace
will
operate
only
in
the
low-
heat
mode.
If
this
condition
is
left
unattended,
the
furnace
will
eventually
lockout.
It
is
recommended
that
the
furnace
filter
be
checked
every
3
or
4
weeks
and
cleaned
if
necessary.
The
air
filter
is
normally
located
in
the
blower
compartment.
(See
Fig.
3.)
Filters
for
the
downflow
furnaces
are
normally
lo¬
cated
in
the
return-air
plenum
above
the
blower.
If
the
filters
have
been
installed
in
another
location,
contact
your
dealer
for
instructions.
To
inspect,
clean
and/or
replace
the
air
filter(s),
follow
these
steps:
UPFLOW
FURNACES
ONLY:
1.
Turn
OFF
the
electrical
supply
to
the
furnace.
(See
Fig.
19.)
2.
Remove
control
and
blower
access
doors.
(See
Fig.
21
and
22
.
)
3.
Push
filter
retainer
toward
the
back
of
the
furnace
until
it
clears
the
flange
on
the
furnace
casing.
(See
Fig.
23.)
6

Related product manuals