EasyManuals Logo

Bryant Preferredt Series User Manual

Bryant Preferredt Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
25
WHILE IN CONFIGURATION MODE
The option number is displayed in the heat setpoint location and the configuration
setting is displayed in the cool setpoint location. On the T6- PAC01- A/PHP01-A
(programmable) models, a box will surround the option number. The mode button
is used to move the box between the two displayed values. The soft keys below the
listed values may also be used to move the box between selected values. The value
inside the box is changed by using the UP/DOWN buttons. On the
T6 - NAC01 - A/NHP01 - A (non - programmable) models, one of the values will be
flashing. The mode button is used to change which value is flashing or the Home
and Sleep buttons may also be used to select which v alue to flash. The value that is
flashing is changed by using the UP/Down buttons. All changes made are saved at
the time of selection and will be saved in the event o f the 3 minute time- out or
when installer exits from configuration menu.
Configuration Options —Selection
Option 01 Equipment Type
HP model Range: HP, AC, H, C, H2, A2.
AC model Range: AC, H, C.
HP operates a single- speed heat pump with a fan coil.
AC operates a single- speed AC.
H operates a heat- only system. Furnace or fan coil only;
no outdoor unit.
C operates a cool only - system. Outdoor AC unit with an
indoor fan coil with no strip heaters.
A2 2-stage air conditioner with a furnace or fan coil.
H2 2- stage heat pump with a fan coil.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant Preferredt Series and is the answer not in the manual?

Bryant Preferredt Series Specifications

General IconGeneral
BrandBryant
ModelPreferredt Series
CategoryThermostat
LanguageEnglish

Related product manuals