• Spin dial one click to the right. “BLDG RESP” will now be displayed. This value
accounts for the building’s insulation factor – 1 being the lowest, 2 being
medium, and 3 being the best. The factory setting is “2”. Press and hold the
“Enter” button and spin the dial to the desired setting. Release “Enter” button
when desired value is displayed.
• Spin dial one click to the right. “PUMPLOGIC” will now be displayed. This
temperature setting will dictate at what temperature the boiler must be before
the heating circulator cycles. Factory setting is 104°F. Raising this temperature
will help to raise the heat curve for outdoor reset. To change this setting, press
and hold the “Enter” button while spinning the dial. For higher temperature
systems such as baseboard, radiators, and fan coils, you should raise this setting
to these suggested values:
• Turn the dial one click to the left and “MAX TEMP1” will be displayed. This will
act as a high limit setting for the boiler. Factory setting is 176°F. Press and
hold the “Enter” button while spinning the dial to your desired setting. When
desired setting is reached, let go of the “Enter” button.