TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
The STB safety thermostat has been
triggered.
Upon reaching a temperature of 95°С, the thermostatic
safety protection device is triggered and the fan is turned
off. To resume protection, remove the black cap on the
back panel of the boiler and press the button on the STB-
thermostat. Contact your installer to determine the cause of
protection triggering.
Lowboilertemperature.
Unabletoreachnormaltemperaturemodeof65°-85°С
Cause Solution
Inadequate sizing and/or
combinaon of heang appliances
Immediately consult your installer about the problem.
Ejeconofunburnedpelletsintothecombusonchamberoftheboiler
Cause Solution
Poor adjustment of the fuel-to-air
rao from the burner controller
Contact your installer. It is necessary to set the burner
properly using gas analyzer
Ulizaon of low-quality pellets Use only fuel which meets the requirements specied in the
manual. (see secon 3. Fuel)
Formaonofclinkersandnoncombusbleinclusionsinsideburnerbody
Cause Solution
Ulizaon of low-quality pellets
(see secon 3. Fuel)
Use only fuel which meets the requirements specied in the
manual.
Low performance of the automac
cleaning system
Increase the frequency of inclusions of self-cleaning system
Improper seng of fuel-air mixture Adjust using gas analyzer
Boilertemperaturetoohigh.Controllerfailure
Cause Solution
Grid power uctuaons
It is mandatory to assure a backup power generator of
corresponding rated power! (see table 1)
Power failure
High temperature of exhaust gases.
High temperature alarm is turning
on
Fume exhaust tubes of boiler water jacket are clogged with
soot. Reduced heat transfer. The boiler should be cleaned.
Please contact an authorized specialist / service shop to
clean the boiler.
High temperature in boiler water
jacket and low temperature in the
buer tank.
1. Incorrect ON/OFF temperature sengs of pumps.
2. Incorrect sizing of heang system.
Boilerwatertoohot,heangbodiestoocold
Cause Solution