On selecting P RO TE CT IO N by pressing
ENTER key, User can see the list of all the
protection parameters by using the scroll keys.
Press ENTER to select the desired Parameter &
use Scroll keys to Edit the selected parameter. To
save the desired changes, user have to enter the
correct password by selecting the YES option.
#COMMON SET#
Ip : 1A
In : 1A
P-CTRatio : 0001
E-CTRatio : 0001
ResetDly : 00.0s
Flt-PopUp : YES
←BACK
#50/51/N#
PhaseCh : DEFT
EarthCh : DEFT
I> : EXIT
ti> : 0.050
t> : 000.10s
I>> : EXIT
t>> : 00.10s
I>>> : EXIT
t>>> : 00.10s
Ie> : EXIT
tie> : 0.050
te> : 000.10s
Ie>> : EXIT
te>> : 00.10s
Ie>>> : EXIT
te>>> : 00.10s
t_TCS : EXIT
tCBFP : EXIT
CBFP Lvl : 5%
←BACK
# FAULT NUMBER #
SELECT : 02
On selecting FAULT RECORD, by pressing
ENTER key, Fault no. screen appears. By using
ENTER & Scroll keys select the desired Fault no.
for its details.
On selecting COMMON SETTING by pressing
ENTER key, User can see the list of all the
parameters by using the scroll keys. Press
ENTER to select the desired Parameter & use
Scroll keys to Edit the selected parameter. To save
the desired changes, Press ENTER key and than
have to enter the correct password by selecting
the YES option.
From Menu-1 :
From Menu-1 :
From Menu-1 :
11