11. Under Activities à Alarm and event
management à Alarm conditions. Click Add
and enter the name of the alarm condition (e.g.:
“no showcase communication “).
12. Choose the device and the alarm variable to be
checked.
13. Click È to add the variable.
14. Repeat to add the number of variables that need
to be checked.
15. Click Add: the new condition is added to the list
of conditions.
Warning: the message area shows a notifi cation
requiring the engine to be restarted and the direct
command to do so. This means boss needs to be
restarted to make the changes eff ective.
Note:
• to set a single rule for all site alarm conditions,
select “All alarms”.
• set a rule for all alarm conditions based on priority,
select the priority to be managed under Priority.
16. Under Activities à Alarm and event
management à Rules enter the name of the
rule (e.g.: “email no showcase communication”).
17. Choose the alarm condition or event (e.g.: “No
showcase communication “).
18. Choose the time band in which the action is
enabled (e.g.: “dayshift weekdays”).
19. Choose the action (e.g.: “email to service”)
20. Defi ne the delay for the action
21. Enable the rule
22. Click Add: the new rule is added to the list.
23. Click Save.
24. Restart the engine.