What causes incorrect superheat value measured by Carel EVD ice?
- AAshley WeissAug 18, 2025
If the superheat value measured is incorrect, it could be due to a couple of reasons. First, the probe might not be measuring correct values. Check that the pressure and the temperature measured are correct and that the probe position is correct. Check the selection of pressure probe. Check the correct probe electrical connections. Also, the type of refrigerant set could be incorrect. Check and correct the type of refrigerant parameter.