52
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
9. SOFTWARE UPDATE
9.1 Setting the controller’s address
The controller’s pLAN address set by default in the factory is 1. The
controller’s address can be set via a terminal connected in the pLAN
network. The controller is assigned a private (Pr) or shared (Sh) terminal
with address 32. The address of the external terminal can be set in the
range between 0 and 32; addresses between 1 and 32 are used by the
pLAN protocol, while address 0 identifi es the Local terminal protocol,
used for point-to-point connections and to confi gure the controller (this
procedure is only possible with a pGD terminal and one pCO only).
If the controller with the default setting (address=1) is connected to an
external terminal (address=32), communication is established and the
display on the external terminal replicates the display on the built-in
terminal, if featured. If, on the other hand, the controller has a diff erent
address (e.g. 7) and the terminal is not set to communicate with the
controller with this address, once the connection has been established,
the terminal displays a blank screen.
In this case, proceed as follows.
Procedure:
1. Press the UP, DOWN and Enter buttons together to access the
screen for setting the terminal’s address.
Display address
setting............:02
I/O Board address..:07
2. Set the address of the display, 0 for point-to-point connections.
Confi rm by pressing Enter.
Display address
setting............:00
3. Power off the controller.
Slave1
Fig. 9.a
4. Power on the controller while holding the Alarm and Up buttons
together, until the following screen is shown.
selftest
please wait...
5. Use UP and DOWN to set the controller’s pLAN address to 7 and
confi rm by pressing Enter.
pLAN address: 7
UP: increase
DOWN: decrease
ENTER: save & exit
9.2 Setting the terminal’s address and
connecting the controller to the terminal
After setting the controller’s network address (see previous paragraph),
to establish connections between the controller and the terminal, the
terminal’s address needs to be set.
Procedure:
1. Press the UP, DOWN and Enter buttons together. The screen is
displayed for setting the terminal’s address. Set the address to 2 and
confi rm by pressing Enter.
Display address
setting............:02
2. Press the UP, DOWN and Enter buttons together. Press Enter twice and set
the controller’s address to 7. Confi rm by pressing Enter.
Display address
setting............:02
I/O Board address..:07
3. Confi rm by pressing Enter.
Terminal config
press ENTER
to continue