53
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
4. Set terminal 1 (Trm1) with address 2 as private (Priv) or shared
(Shared) according to the application, and confi rm to exit. After a few
seconds, the connection will be established.
P:07 Adr Priv/Shared
Trm1 02 Pr
Trm2 None --
Trm3 None -- Ok? Yes
5. To add a second terminal, repeat steps 1 to 4.
9.3 Uploading/updating the software
The following methods can be used to update the fi rmware and acquire
the log fi les on pCO controllers:
SmartKey programming key;
pCO manager tool, installable on a PC.
Smart key
The PCOS00AKY0 key is an electronic device used to program and service
the pCO sistema family controllers. PCOS00AKY0 simplifi es data transfer
between the controllers installed and a personal computer by exploiting
the high capacity fl ash memory for storing software applications, BIOS and
variable logs. The pCO is connected directly via the telephone connector
using the cable supplied, while to transfer the data to a personal computer,
the USB adapter code PCOS00AKC0 is required. The power supply comes
either via the USB port on the PC or from the controller, therefore no
external power supply is needed.
USB
telephone cable
start
mode
PCOS00AKC0
USB
Fig. 9.b
For the steps in the procedure, see par. 9.1.
Operating instructions
start
mode
start
mode
Fig. 9.c
Programming the Smart Key via Personal Computer
The operating modes described in the table below can be confi gured
using a program on the PC. The program can also load the software to the
key or transfer logged data from the controller to disk.
Type Function Mode button
B Update software from key to pCO (BIOS,
application, parameters, etc.)
Disabled
C* Copy software from pCO to pCO (BIOS,
application, parameters, etc.)
Switches the key from write
mode to read mode
D Read logs Disabled
E Read logged data and software from
pCO (BIOS, application, parameters, etc.)
Disabled
F Read logged data Disabled
G Copy from pCO to pCO and read logs Switches the key to write mode,
read mode and read logs mode
*: Default mode
Tab. 9.d
The key is factory-programmed in read/write mode (type C) so that it can
be used immediately to transfer software from one controller to another.
When the key is connected to the personal computer, the symbols have
the following meanings:
Flashing Waiting for connection to PC
Alternating
When connected to PC indicates data transfer in progress
The programming key is compatible starting from BIOS version 3.43 and
BOOT version 3.01. For more detailed information on programming the
key, see the pCO Manager program manual.
Using the Smart Key with the pCO/μPC
Switch off the pCO, remove any peripherals connected in the pLAN
and plug the key into the telephone connector on the controller. When
switching on again, all the symbols light up momentarily and the buzzer
emits a beep. A few seconds later the key becomes operational. During
this period the symbols
will fl ash. The controller then enters
programming mode and the start button lights up steadily. Press the
button to start data transfer.
Important:
If the key is type B, C or G (in write mode) pressing the start button will
immediately delete the software already loaded on the pCO.
Do not remove the key while data is being transferred to the key itself,
as the fi le being transferred will be lost and the corresponding space
will not be restored. To restore the original capacity all the fi les will
need to be deleted. If the key is type “C or “G”, simply perform a new
application read operation.
Meanings of Buttons/Symbols
Flashing: the key is connecting to the pCO. During this phase, which
may last a few seconds, the start button is disabled.
start
Flashing: The key has detected the pCO and is checking the access
rights.
start+
On steady: Pressing the start button will start writing the software to
the pCO.
start+
On steady: Pressing the start button will start reading the software
from the pCO.
start+
On steady: Pressing the start button will start reading the logs from
the pCO.
mode
On steady: In case of C or G keys, pressing the button for 1 second
switches from read to write.
Tab. 9.b
If the key is type C of G, pressing the “mode” button for 1 second switches
from read to read logs (G only) or to write. The symbols
(write to pCO),
(read from pCO), (read logs) refl ect the selected status. If the key
is not type “C” or “G”, the “mode” button is disabled and off . The “start
button starts the read or write operation, indicated by the fl ashing of the
corresponding symbol ( or ) at a frequency proportional to the
progress of the operation.
When the operation is completed, the buzzer will sound intermittently
for 2 seconds. Pressing the start button again will make the buzzer sound
without repeating the operation. To repeat the operation, the key must
rst be unplugged. In case of error the symbol will light up together with
the other LEDs. The following table can help you fi nd the cause of the
problem.