54
ENG
Heos +0300078EN - rel. 1.6 - 23.11.2017
Errors before pressing the START button
+ +
Symbols fl ashing
Communication error: No response from the
pCO or: Key fi rmware version is incompatible
+mode
Symbols steady Password error
+mode
Symbols fl ashing Type of key is incompatible
+
Symbols steady The key is missing one or more required fi -
les (memory empty; no kit for the type of
pCO connected)
+ +start
Symbols steady +
fl ashing start
Incompatibility between the software on
the key and the pCO HW
+ +mode
Symbols steady +
fl ashing mode
Incompatibility between pCO application
and HW (application size)
+ +
Symbols steady No logged data present on the pCO
Steady Type of key not programmed.
Tab. 9.e
Errori dopo la pressione del tasto START
+start+ +buzzer
Symbols fl ashing
and buzzer sounding
intermittently
Write operation failed
+start+ +buzzer
Symbols fl ashing
and buzzer sounding
intermittently
Read operation failed
+start+ +buzzer
Symbols fl ashing
and buzzer sounding
intermittently
Read logs operation failed
+ +
Symbols steady +
fl ashing
Incompatibility between log
confi guration and pCOHW (no
fl ash memory). This error does
not prevent writing other fi les.
+
Steady Insuffi cient space to read logs
Flashing Generic error
Tab. 9.f
9.4 pCO Manager: operating instructions
pCO Manager is a program that lets you manage all the confi guration,
debugging and maintenance operations on pCO Sistema devices. pCO
Manager can be installed by itself or as part of the 1Tool programming
environment.
Installing pCO Manager
Go to http://ksa.carel.com and, in section pCO Sistema, select pCO_manager.
After you accept the general conditions of the software’s free use licence,
a window will open from which you can download the fi le pCO_manager.
zip. Install the program on your computer.
Connecting the PC to the pCO controller
Connect a cable with USB/RS485 converter to the USB port on the
computer, and connect the converter to a telephone cable plugged into
the pLAN port of the pCO.
USB
CVSTDUTLF0
power supply
USB
Fig. 9.g
Upon launching, pCO Manager will display a screen showing the
connection settings in the upper right-hand corner. Choose:
1. “connessione locale” [local connection];
2. baud rate: Auto;
3. “ricerca dispositivo” [fi nd device]: Auto (pLAN).
As for the port number, follow the Wizard’s instructions for the port to be
identifi ed automatically (e.g. COM4).
Fig. 9.h
Switch the controller off and then on again and use the Connect
command to establish the connection. When the connection is
established the fl ashing message “ONLINE” will appear at the bottom left
of the screen.
Fig. 9.i
Installing the application program
• Select the directory containing the application program fi les and click
“Upload” to upload the program to the pCO controller.
Fig. 9.j
Commissioning
• Using the mouse, select “Commissioning” at the bottom left. A new
work environment will appear.
Fig. 9.k
• Click on “confi gura dispositivo” [confi gure device] to display all the
application variables. The variables can be selected according to the
categories that appear at the bottom.
Fig. 9.l