EasyManuals Logo

Carel µC2SE User Manual

Carel µC2SE
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
27
ENGLISH
µC
2
SE - +030220426 - rel. 2.0 - 03.08.2009
4.3.3 Antifreeze/support heater setting parameters (A*)
display
indicat.
parameter and description default
level
min. max. UOM variat. default visibility supervis.
variable
Modbus variable
type
A01 Alarm set point antifreeze/low ambient temperature (air/air) U A07 A04 °C/°F 0.1 30 - 11 (R/W) 11 Analog
A02 Differential for antifreeze/low ambient temperature alarm (air/air) U 3 1220 °C °F 0.1 50 - 12 (R/W) 12 Analog
A03 Bypass time for antifreeze alarm/low ambient temp. when turning on the unit
in heating mode
U 0 150 s 1 0 - 22 (R/W) 229 Integer
A04 Set point for the activation of antifreeze heater/auxiliary heater U A01 r16 °C/°F 0.1 50 AA 13 (R/W) 13 Analog
A04 Antifreeze/support heater set point differential U 0 200 °C/°F 0.1 70 AR 77 (R/W) 77 Analog
A05 Diff. for antifreeze heater/auxiliary heater U 3 500 °C/°F 0.1 10 - 14 (R/W) 14 Analog
A06 Auxiliary heater probe
0= Control probe see (see Table 5.a)
1= Antifreeze probe see (see Table 5.a)
F 0 1 Flag 1 0 - 6 (R/W) 6 Digital
A07 Antifreeze alarm set point limit F -400 1760 °C °F 0.1 -400 - 15 (R/W) 15 Analog
A08 Auxiliary heater set point in heating mode U A01 r16 °C °F 0.1 250 AA 16 (R/W) 16 Analog
A08 Antifreeze/support heater set point differential U 0 200 °C °F 0.1 70 AR 78 (R/W) 78 Analog
A09 Auxiliary heater differential in heating mode U 3 500 °C/°F 0.1 30 - 17 (R/W) 17 Analog
A10 Antifreeze automatic start up
0= disabled function
1= Heaters and pump on at the same time on A4/A8
2= Heaters and pump on indipendently on A4/A8
3= Heaters ON on A4/A8
U 0 3 1 0 - 23 (R/W) 230 Integer
A11 Auxiliary heater 2 set point in heating U A01 r16 °C/°F 0.1 250 AA 67 (R/W) 67 Analog
A11 Support heater 2 differential in heating U 0 200 °C/°F 0.1 70 AR 79 (R/W) 79 Analog
A12 T diff. set point for dirty fi lters (air/air) U 0 1760 °C/°F 0.1 150 - 57 (R/W) 57 Analog
A13 Outlet limit set point in freecooling conditions U A07 r16 °C/°F 0.1 30 - 80 (R/W) 80 Analog
A14 Antifreeze alarm set point from EVD U A07 A04 °C/°F 0.1 30 - 82 (R/W) 82 Analog
Table 4.c
4.3.4 Probe reading parameters (b*)
display
indicat.
parameter and description default
level
min. max. U.O.M. variat. default visibility supervis.
variable
Modbus variable
type
b00 Confi g. of probe to be shown on the display
0= probe B1 1= probe B2
2= probe B3 3= probe B4
4= probe B5 5= probe B6
6= probe B7 7= probe B8
8= set point without compensation
9= dynamic set point with possible compensation
10= remote ON/OFF digital input status
11= µAD probe
U 0 11 N 1 0 - 24 (R/W) 231 integer
b01 Value read by probe B1 D 0 0 °C /°F - 0 - 102 (R) 102 Analog
b02 Value read by probe B2 D 0 0 °C /°F - 0 - 103 (R) 103 Analog
b03 Value read by probe B3 D 0 0 °C /°F - 0 - 104 (R) 104 Analog
b04 Value read by probe B4 D 0 0 °C /°F/Dbar - 0 - 105 (R) 105 Analog
b05 Value read by probe B5 D 0 0 °C /°F - 0 X 106 (R) 106 Analog
b06 Value read by probe B6 D 0 0 °C /°F - 0 X 107 (R) 107 Analog
b07 Value read by probe B7 D 0 0 °C /°F - 0 X 108 (R) 108 Analog
b08 Value read by probe B8 D 0 0 °C /°F/Dbar - 0 X 109 (R) 109 Analog
b09 Driver 1 evaporator temperature D 0 0 °C /°F - 0 V 110 (R) 110 Analog
b10 Driver 1 evaporator pressure D 0 0 Dbar - 0 V 111 (R) 111 Analog
b11 Driver 1 superheating D 0 0 °C /°F - 0 V 112 (R) 112 Analog
b12 Driver 1 saturation temperature D 0 0 °C /°F - 0 V 113 (R) 113 Analog
b13 Driver 1 valve position D 0 1000 % - 0 V 114 (R) 114 Analog
b14 Driver 2 evaporator temperature D 0 0 °C /°F - 0 XV 115 (R) 115 Analog
b15 Driver 2 evaporator pressure D 0 0 Dbar - 0 XV 116 (R) 116 Analog
b16 Driver 2 superheating D 0 0 °C /°F - 0 XV 117 (R) 117 Analog
b17 Driver 2 saturation temperature D 0 0 °C /°F - 0 XV 118 (R) 118 Analog
b18 Driver 2 valve position D 0 1000 % - 0 XV 119 (R) 119 Analog
b19 Temp. probe at the outlet of the external coil c1 D 0 0 °C /°F - 0 V 120 (R) 120 Analog
b20 Temp. probe at the outlet of the external coil c12 D 0 0 °C /°F - 0 XV 121 (R) 121 Analog
b21 Terminal probe (for µAD terminal) D -400 800 °C /°F 0.1 0 - 128 (R) 128 Analog
Table 4.d
4.3.5 Compressor setting parameters (c*)
display
indicat.
parameter and description default
level
min. max. U.O.M. variat. def. visib. supervis.
variable
Modbus variabile
type
c01 Minimum on time U 0 999 s 1 60 - 25 (R/W) 232 Integer
c02 Minimum off time U 0 999 s 1 60 - 26 (R/W) 233 Integer
c03 Delay between 2 starts of the same compressor U 0 999 s 1 360 - 27 (R/W) 234 Integer
c04 Delay between starts of the 2 compressors U 0 999 s 1 10 - 28 (R/W) 235 Integer
c05 Delay between 2 shut-downs of the 2 compressors U 0 999 s 1 0 - 29 (R/W) 236 Integer
c06 Delay at start-up U 0 999 s 1 0 - 30 (R/W) 237 Integer
c07 Delay in switching on the compressor after switching on the pump/inlet
fan (air/air)
U 0 999 s 1 20 - 31 (R/W) 238 Integer
c08 Delay in switching OFF the compressor after switching OFF the pump/
inlet fan (air/air)
U 0 150 min 1 1 - 32 (R/W) 239 Integer
c09 Maximum compressor operating time in tandem U 0 60 min 1 0 - 33 (R/W) 240 Integer
c10 Compressor 1 timer D 0 8000 100 hours - 0 - 122 (R) 122 Analog
c11 Compressor 2 timer D 0 8000 100 hours - 0 - 123 (R) 123 Analog
c12 Compressor 3 timer D 0 8000 100 hours - 0 - 124 (R) 124 Analog
c13 Compressor 4 timer D 0 8000 100 hours - 0 - 125 (R) 125 Analog
c14 Operation timer threshold U 0 100 100 hours 1 0 - 34 (R/W) 241 Integer
c15 Hour counter evaporator pump/fan 1 D 0 8000 100 hours - 0 - 126 (R) 126 Analog
c16 Hour counter condenser backup pump/fan 2 D 0 8000 100 hours - 0 - 127 (R) 127 Analog
c17 Minimum time between 2 pump starts U 0 150 min 1 30 - 35 (R/W) 242 Integer
c18 Minimum pump ON time U 0 15 min 1 3 - 36 (R/W) 243 Integer
c19 Delay between valve and compressor U 0 100 s 1 3 - 125(R/W) 332 Integer
Table 4.e

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel µC2SE and is the answer not in the manual?

Carel µC2SE Specifications

General IconGeneral
BrandCarel
ModelµC2SE
CategoryController
LanguageEnglish

Related product manuals