pCO Sistema
Code: +030220336 - rel. 1.5 - 22/12/10
15
Connector
Connector Connector
Connector
Signal
Signal Signal
Signal
Description
DescriptionDescription
Description
J5-2 ID2 digital input no. 2, 24 Vac/Vdc
J5-3 ID3 digital input no. 3, 24 Vac/Vdc
J5-4 ID4 digital input no. 4, 24 Vac/Vdc
J5-5 ID5 digital input no. 5, 24 Vac/Vdc
J5-6 ID6 digital input no. 6, 24 Vac/Vdc
J5-7 ID7 digital input no. 7, 24 Vac/Vdc
J5-8 ID8 digital input no. 8, 24 Vac/Vdc
J5-9 IDC1 common for digital inputs from 1 to 8 (negative pole for DC power supply)
J6-1 B7 passive analogue input 7 (NTC)
J6-2 GND common for analogue input 7
J6-3 B8 passive analogue input 8 (NTC)
J6-4 GND common for analogue input 8
J7-1 ID9 digital input no. 9, 24 Vac/Vdc
J7-2 ID10 digital input no. 10, 24 Vac/Vdc
J7-3 ID11 digital input no. 11, 24 Vac/Vdc
J7-4 ID12 digital input no. 12, 24 Vac/Vdc
J7-5 IDC9 common for digital inputs from 9 to 12 (negative pole for DC power supply)
J8-1 ID13H digital input 13, 230 Vac
J8-2 ID13 digital input 13, 24 Vac/Vdc
J8-3 IDC13 common for digital inputs 13 and 14 (negative pole for DC power supply)
J8-4 ID14 digital input 14, 24 Vac/Vdc
J8-5 ID14H digital input 14, 230 Vac
J9-1 + 5 V ref power supply for 0/5 V ratiometric probes
J9-2 GND power supply common
J93 + Vterm additional power supply terminal for Aria
J10 6-pin telephone connector for connection to the standard user terminal
J11-1 TX- RX-/TX- connector for RS485 connection to the pLAN network
J11-2 TX+ RX+/TX+ connector for RS485 connection to the pLAN network
J11-3 GND GND connector for RS485 connection to the pLAN network
J12-1 C1 common for relays: 1, 2, 3
J12-2 NO1 normally open contact, relay no. 1
J12-3 NO2 normally open contact, relay no. 2
J12-4 NO3 normally open contact, relay no. 3
J12-5 C1 common for relays: 1, 2, 3
J13-1 C4 common for relays: 4, 5, 6
J13-2 NO4 normally open contact, relay no. 4
J13-3 NO5 normally open contact, relay no. 5
J13-4 NO6 normally open contact, relay no. 6
J13-5 C4 common for relays: 4, 5, 6
J14-1 C7 common for relay no. 7
J14-2 NO7 normally open contact, relay no. 7
J14-3 C7 common for relay no. 7
J15-1 NO8 normally open contact, relay no. 8
J15-2 C8 common for relay no. 8
J15-3 NC8 normally closed contact, relay no. 8
J16-1 C9 common for relays: 9, 10, 11
J16-2 NO9 normally open contact, relay no. 9
J16-3 NO10 normally open contact, relay no. 10
J16-4 NO11 normally open contact, relay no. 11
J16-5 C9 common for relays: 9, 10, 11
J17-1 NO12 normally open contact, relay no. 12
J17-2 C12 common for relay no. 12
J17-3 NC12 normally closed contact, relay no. 12
J18-1 NO13 normally open contact, relay no. 13
J18-2 C13 common for relay no. 13
J18-3 NC13 normally closed contact, relay no. 13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel pCO3 series and is the answer not in the manual?

Carel pCO3 series Specifications

General IconGeneral
Protection RatingIP20
Communication PortsRS-485
DisplayGraphic LCD with backlight
Power Supply24 Vac/dc ±10%
Storage Temperature+70°C
Humidity10% to 90% non-condensing