33
Properties Menu Navigates to Property pages
Login with one of the following passwords:
User level - type user
Admin level - type admin
- Unit configuration
- Sensor configuration
- Setpoints Password Level: None
- Alarm configuration
- Maintenance
- Service test
- Touchscreen setup
Factory level - type Touch
- Startup wizard
- ET (Equipment Touch) system
NOTE: Only the buttons that are authorized for a spe-
cific password level are visible.
Password Level: None
Properties/Status This menu shows the status or value of the listed point.
Password Level: None
Properties /
Unit Configuration
Cooling Lockout
Default: 50
Ra
nge: –20 to 80°F
Does not allow free cooling mode if OAT is above this
temp.
Cooling Lockout Offset
Default: 3
Range: 1 to 10°F
Increases the Lockout setpoint by the value of the setting.
Password Level: Admin
Properties /
Sensor Calibration
Allows calibration of sensor.
Default: 0
Ra
nge: –10 to 10°F
Password Level: Admin
Table 8 — App Controller Screen Navigation (cont)
SCREEN NAMES DISPLAY DETAILS