34
Properties / Setpoints Default: 44°F
Range: 15 to 75°F
Password Level: Admin
Properties /
Alarm Configuration
LWT
lo 42 (Range: –45 to 45°F)
hi 125 (Range: –20 to 150°F)
EWT
lo 42 (Range: –45 to 45°F)
hi 125 (Range: –20 to 150°F)
OAT
lo –65 (Range: –65 to 40°F)
hi 245 (Range: 100 to 245°F)
Non-Operational Comp
This drives the Non-Operational Component alarm.
The is the alarm offset value.
CWST
This is a low limit alarm offset.
Reverse Load Water Flow
This alarm detects incorrect flow direction. Default is
2°F.
Password Level: Admin
Properties / Maintenance Values show current status of these points.
Password Level: Admin
Table 8 — App Controller Screen Navigation (cont)
SCREEN NAMES DISPLAY DETAILS